SBN TANK TYPE COMMERCIAL GAS WATER HEATER

SERVICE HANDBOOK

TEST 10 - MAIN BURNER IGNITION FOR LESS THAN 5 SECONDS

Conditions:

ƒPower On – plug connected

ƒMain Burner ignites for approximately 5 seconds then goes out.

ƒTests 8 and 9 completed

ƒNote flash code on ignition board LED.

Hot Surface Igniter

Pin 2

Main Burner

E1, Pin 2 - From Flame Proving Rod

(Illustration of low NOx burner)

TEST 10

Flame Prover Circuit Check

If…

...then

 

no extended main burner igntion

Œcheck wiring and plug connections of HSI assembly

 

 

plug and ignition board receptacles E1, Pin 2

 

 

Œcheck that HSI assembly is not cracked or dirty

 

 

Œcheck that flame prover will be in main flame

 

 

Œreplace HSI assembly

 

 

 

 

still no extended main burner ignition

replace ignition control board

 

 

 

 

Technical Training Department

35

©2003

 

 

Ashland City, Tennessee

Page 36
Image 36