SBN TANK TYPE COMMERCIAL GAS WATER HEATER

SERVICE HANDBOOK

Exterior Clearance

The illustration below shows the required clearances for venting units using natural draft venting.

Required Exterior Clearances

“Copyright by the American Gas Association. Used by permission of the copyright holder”.

The vent must extend at least 3 feet above the highest point where it passes through a roof of a building and at least 2 feet higher than any portion of a building within a horizontal distance of 10 feet (for vents of 12 inches in diameter or less).

References: NFPA 54 ANSI Z 223.1 SEC 7.5.2a and Sec 7.6.2a may allow reduction to 8 feet with a “listed vent cap.”

Technical Training Department

5

©2003

Ashland City, Tennessee

Page 6
Image 6
State Industries STC-074 specifications Required Exterior Clearances