SBN TANK TYPE COMMERCIAL GAS WATER HEATER
SERVICE HANDBOOK
Often, it is more practical to install vertical
Make-Up Air - Vertical Ducts
Again, two openings are required: one within 12 inches of the top of the enclosure and one within twelve inches of the bottom of the enclosure. Each opening must have a free area of not less than 1 square inch per 4,000 BTUH of the total input of all appliances within the enclosure.
Make-Up Air - Horizontal Ducts
When the heater is installed in an interior room with no roof access for vertical ducts, horizontal
©2003 | 8 | Technical Training Department |
Ashland City, Tennessee