SBN TANK TYPE COMMERCIAL GAS WATER HEATER

SERVICE HANDBOOK

CONTROL BOARD DIAGNOSTIC LED INTERPRETATION AND

TROUBLESHOOTING

TEST 1 - 120 VAC CHECK TO WATER HEATER

Conditions:

ƒNo Green display “Power” LED on.

ƒPlugs are in receptacles.

ƒSupply power breaker is not “open”

ƒOn/Off heater switch is “On”.

Water Heater

Control

Ignition Control Board

TEST 1

120 Vac Check To Water Heater On Switch

ŒCheck for 115-125 VAC black wire to ground

Œ115 V check to E13 terminal and 2B receptical.

If…

...then

 

 

voltage is not present from on/off switch-

Œcheck conditions above

 

 

center black wire to ground

Œcheck wiring from switch to break box

 

power is present from center on/off

check power from on/off to ignition board term

 

terminal

E13.

 

 

 

Œcheck wiring from on/off. Left-outside terminal

 

voltage is not present at E13 to ground

to E13.

 

 

 

Œreplace on/off switch.

 

 

power is present at E13

check power from E14 to heater control E2

 

receptacle

 

 

 

 

 

voltage is not present from heater control

Œcheck wiring from ignition control board E14 to

 

heater control receptacle E2.

 

receptacle E2 black to ground

 

Œreplace ignition control board.

 

 

 

power is present at E2

green LED should be on.

 

 

 

 

 

 

©2003

26

Technical Training Department

Ashland City, Tennessee

Page 27
Image 27
State Industries STC-074 specifications Conditions, Water Heater Control Ignition Control Board