SBN TANK TYPE COMMERCIAL GAS WATER HEATER

SERVICE HANDBOOK

FLASH CODES OF DIAGNOSTIC INDICATOR

Conditions:

ƒPower On

ƒRed, heater control “Call for Heat” LED – on

ƒRed, ignition control board diagnostic LED – Flashing

ƒNote LED Flash Code before resetting heater.

LED Status

Indication

1

Flash

System is in lock out.

2

Flashes

Draft proving (pressure) switch failed to open within 5 seconds at the end of the last cycle.

 

 

 

3

Flashes

Draft proving (pressure) switch failed to close ( -2.1 inches of water column pressure) within 5

 

 

seconds after the inducer was started.

 

 

The low gas pressure switch )closes at 5.2" ± .04" w.c.) may have remained open.

 

 

 

4

Flashes

Open on high temperature limit switch (ECO).

6

Flashes

115-volt supply power connection is indicating reversed polarity.

7

Flashes

Flame sensor reads a low flame signal for more than 4.25 sec.

8

Flashes

No ignition sensed.

Continuous Flash

Continuous flame sensed for more than 5 seconds without gas valve being energized.

 

 

Continuous ON

Internal control board failure.

*Control system self adjusts to use a minimum voltage for ignition. Lower voltage results in lower igniter temperature which results in longer igniter life. Igniter voltage may vary from Nominal 80 VAC.

TEST 2 - POLARITY CHECK

Conditions:

 

ƒ No hot water

Display

ƒ Green “Power” LED is on.

 

ƒ Tank is more than 5° F

 

below temperature dial

 

setting.

 

ƒ Red ignition control board

 

diagnostic LED is flashing

 

6 times between pauses.

 

ƒ Red, diagnostic “Call for

 

Heat” LED-OFF.

 

LED’s

Continued on next page

Technical Training Department

27

©2003

Ashland City, Tennessee

Page 28
Image 28
State Industries STC-074 specifications Flash Codes of Diagnostic Indicator, Test 2 Polarity Check