SBN TANK TYPE COMMERCIAL GAS WATER HEATER

SERVICE HANDBOOK

LED INDICATORS ON HOT SURFACE IGNITION (HSI)

USING FLASHING RED LED ON HSI (HOT SURFACE IGNITION)

 

LED STATUS

INDICATION

ACTION TO BE TAKEN

 

 

1 Flash

System is in lockout.

Interrupt power to

 

 

 

 

reset. Heater had not

 

 

 

 

sensed the flame

 

 

 

 

check gas supply and

 

 

 

 

igniter condition.

 

 

2 Flashes

Draft proving

Test for defective

 

 

 

(pressure) switch

switch or a

 

 

 

(closes at -2.10 +0.01

pressurized room

 

 

 

inches W.C. negative

condition that may be

 

 

 

pressure) failed to

forcing air through the

 

 

 

open within 5 seconds

inducer.

 

 

 

at the end of the last

 

 

 

 

cycle.

 

 

 

3 Flashes

Draft proving

Check the draft.

 

 

 

(pressure) switch

The low gas pressure

 

 

 

failed to close

switch closes at 5.2 inches W.C.

 

 

 

within 5 seconds after

may have remained open.

 

 

 

the inducer was

Verify the supply gas pressure

 

 

 

started.

while the gas is flowing.

 

 

 

 

 

 

 

4 Flashes

Open on high

Check temperature

 

 

control operation.

 

 

 

temperature

 

 

 

 

limit switch

 

 

 

 

(ECO)

 

 

 

6 Flashes

115-volt supply power

Verify that a neutral-to-ground

 

 

check results

 

 

 

connection is

in “0” volts and a hot-to-

 

 

 

indicating reversed

ground check

 

 

 

polarity.

results in 115-125 VAC.

 

 

 

 

 

 

 

 

 

 

 

©2003

38

Technical Training Department

Ashland City, Tennessee

Page 39
Image 39
State Industries STC-074 specifications Eco