11-5 CONDENSER
Measurement of capacity substitutes for checking the condenser. The capacity of the condenser cannot be measured by using the circuit tester. Therefore. the generator is run with a new condenser to seewhether or not the generator performs normally. If the generator performs
Reference: If an instrument ii available for measuring the capacity of the condenser, the total capacity range should be 70
to 7 7pF fat 20°C).
When the condenser displays its total capacity within this range, it is normal.
11-6 RECTIFIER
Using the circuit tester. measure the resistance between each of the two terminals of the rectifier. The rectifier is considered normal when the respective resistanceshave the values specified below.
NOTE: Each of the given values changes with the polarity
of the circuit tester.
Green | Red | White@ | [ |
@ | 01 | 3 | :...16RI |
#3 |
| ...160 1 |
\ | , |
| Y |
The polarity of the circuit tester
Table 7