8.4Grounding Wire
WARNING
Be sure to ground the UPS and ancillary cabinets as specified.
Using the UPS and ancillary cabinets without a proper ground will deteriorate the insulation, cause leakage of currents and electric shock. The resistance to ground should be 10 ohms or less.
The earth grounding bus for 431A and 431B are located inside, at the
The earth grounding bus for 431M is located on the right side wall just above the
Use a AWG 2 (or 38 mm2) or larger cable for the grounding wire. Run the grounding wire through the opening at the bottom, through a hole in the top knockout plate or through the side access hole. Connect the grounding wire to the earth ground bus.
The ground wire must have a crimp terminal with a 3/16 in. (4.76 mm) diameter screw hole. The ground bus has twelve (12) 0.163 in. (4.1 mm) holes tapped for a 10/32 screw. Connect the crimp terminal and ground bus together using a 10/32 screw.
Figure 8-4 - Example: UPS Ground Bus
20 | 4300 Series Ancillary Cabinets Installation and Operation Manual |