13.8MBS Operation
Switch MBS from on-line to Bypass (Solid lines)
The 431M Mechanical Interlock Plate is locked in the
1.Place the UPS in static bypass. The Bypass indicator light on the 431M should illuminate and the interlock solenoid will retract.
NOTE: If the Bypass indicator light DOES NOT ILLUMINATE in bypass mode, contact Toshiba Field Service immediately.
2.Slide the Mechanical Interlock Plate to the center position as shown in Figure
3.Switch CB2 ON (up) as shown in Figure
4.Switch CB3 OFF (down) and CB1 OFF (down), as shown in Figure
5.Slide the mechanical Interlock Plate to the left position as shown in Figure
6.The circuit breakers are now locked in Maintenance Bypass position.
CB1
CB2
CB3
(A) | (B) |
| CB3 |
(C) | (D) | (E) |
|
|
Maintenance Bypass to
Figure 13-8 - MBS Mechanical Interlock Plate Operation
Switch MBS from Bypass to On-Line (Dotted lines)
1.The Maintenance Bypass position is shown in Figure
2.Slide the mechanical Interlock Plate right to the Center position as shown in Figure
3.Switch in order, CB1 ON (up), and CB3 ON (up) as shown in Figure
4.Switch CB2 OFF (down), as shown in Figure
5.Slide the mechanical Interlock Plate to the right position as shown in Figure
6.Place the UPS in
7.The MBS indicator light should extinguish, and the MBS solenoid locks the Mechanical Interlock Plate in place.
4300 Series Ancillary Cabinets Installation and Operation Manual | 59 |