7 Storage/Operating Environment

7.1Storage Environment

Observe the following when storing the ancillary cabinets.

Store ancillary cabinet indoors.

Temperature fluctuations should be minimized.

The optimal storage temperature range is 68 – 77 °F (20 – 25° C).

A maximum temperature range of 32 – 104 °F (0 – 40 °C) should be observed.

The optimal relative humidity at the storage location should be between 50 – 60%.

Humidity must not exceed 90%.

Avoid locations where ancillary cabinet may be exposed to corrosive gas.

Avoid locations with dirt and/or dust.

TABLE 7.1 - UPS STORAGE/OPERATING ENVIRONMENT STANDARDS

Item

Environment standard

 

Storage Location

Indoors

 

Ambient Temperature

Minimum storage temperature: 32 °F (0 °C)

Maximum storage temperature: 104 °F (40 °C)

Relative Humidity

The relative humidity must be between 30 and 90% and without

condensation due to temperature changes.

 

 

This equipment is rated for installations up to 3240 ft. (1000 m)

Altitude

above sea level. Consult with the factory to determine the derating

 

factor for installations above 3240 ft. (1000 m).

Dust

Dust must not exceed normal atmospheric levels and must not

include conductive/corrosive particles, silicone or oils.

 

 

No flammable and/or explosive gas.

 

Hydrogen sulfide (H2S)

Less than or equal to 0.0001 PPM

 

Sulfurous acid gas (SO2)

Less than or equal to 0.05 PPM

 

Chlorine gas (Cl2)

Less than or equal to 0.002 PPM

Flammable Gas

 

 

Ammonia gas (NH3)

Less than or equal to 0.1 PPM

 

Nitrous acid gas (NO2)

Less than or equal to 0.02 PPM

 

Nitrous oxides (NOx)

Less than or equal to 0.02 PPM

 

Ozone (O3)

Less than or equal to 0.002 PPM

 

Hydrochloric acid mist (HCl)

Less than or equal to 0.1 mg/m3

7.2Operating Precautions

Initial startup/commissioning of the ancillary cabinet should be performed by factory authorized personnel.

1)The ancillary cabinet should not be powered up until the entire operation manual has been read. Follow Lockout/Tag Out procedures.

14