4300 Series Ancillary Cabinets Installation and Operation Manual

27

Table 10.3 - 431A Input/Output Power Cable Sizes

(Cable sizes for 75°C Copper Cable)

Recommended/Maximum Wire size and Torque Requirement

Trans-

Code

Input/Output Trans-

Xfmr Type

 

30 kVA

 

 

50 kVA

Tightening

former

 

former Voltage

 

 

 

 

 

Torque

 

 

Phase AWG*

Neutral AWG*

Phase AWG*

Neutral AWG*

Input

B

208V Δ to 208/120V Y

Input Iso

2

- 250 kcmil

 

N/A

2/0 - 250 kcmil

N/A

200 in.-lbs.

 

 

 

 

 

 

 

 

 

 

 

 

C

240V Δ to 208/120V Y

Input Iso

3

- 250 kcmil

 

N/A

1/0 - 250 kcmil

N/A

200 in.-lbs.

 

N

380V Δ to 208/120V Y

Input Iso

6

- 250 kcmil

 

N/A

3

- 250 kcmil

N/A

200 in.-lbs.

 

N

400/415V Δ to 208/120V Y

Input Iso

6

- 250 kcmil

 

N/A

3

- 250 kcmil

N/A

200 in.-lbs.

 

 

 

 

 

 

 

 

 

 

 

 

 

S

480V Δ to 208/120V Y

Input Iso

6

- 250 kcmil

 

N/A

4

- 250 kcmil

N/A

200 in.-lbs.

 

M

600V Δ to 208/120V Y

Input Iso

6

- 250 kcmil

 

N/A

6

- 250 kcmil

N/A

200 in.-lbs.

 

 

 

 

 

 

 

 

 

 

 

X

208/120V Y 4 wire input

N/A

1/0 - 250 kcmil

4/0 - 350 kcmil

 

250 kcmil

350 kcmil

200 in.-lbs.

 

 

(No Transformer)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K

480/277V Y to 208/120V Y

Input Auto

6

- 250 kcmil

3

- 350 kcmil

3

- 250 kcmil

2/0 - 350 kcmil

200 in.-lbs.

 

 

 

 

 

 

 

 

 

 

Output

F

208/120V Y 4 wire input

N/A

1/0 - 250 kcmil

4/0 - 350 kcmil

 

250 kcmil

350 kcmil

200 in.-lbs.

 

 

(No Transformer)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H

208/120V Y to 220/127V Y

Output Auto

1 - 250 kcmil

4/0 - 350 kcmil

4/0 - 250 kcmil

350 kcmil

200 in.-lbs.

 

J

208/120V Y to 240/139V Y

Output Auto

2 - 250 kcmil

3/0 - 350 kcmil

3/0 - 250 kcmil

350 kcmil

200 in.-lbs.

 

P

208/120V Y to 380/220V Y

Output Iso

4 - 250 kcmil

1 - 350 kcmil

1 - 250 kcmil

4/0 - 350 kcmil

200 in.-lbs.

 

 

 

 

 

 

 

 

 

 

Q

208/120V Y to 400/230V Y

Output Iso

4 - 250 kcmil

1 - 350 kcmil

2 - 250 kcmil

3/0 - 250 kcmil

200 in.-lbs.

 

K

208/120V Y to 480/277V Y

Output Auto

6 - 250 kcmil

3 - 350 kcmil

3 - 250 kcmil

2/0 - 250 kcmil

200 in.-lbs.

 

M

208/120V Y to 600/347V Y

Output Iso

6 - 250 kcmil

4 - 350 kcmil

4 - 250 kcmil

1/0 - 250 kcmil

200 in.-lbs.

 

 

 

 

 

 

 

 

 

 

 

 

* Wire capacity for Phase lugs is 250 kcmil - 6 AWG, Neutral lugs is 350 kcmil - 6 AWG.

Page 35
Image 35
Toshiba operation manual 431A Input/Output Power Cable Sizes