Toshiba 431A 12.7 431Bx000xxER111 Backup Runtime Tables, 431B Typical Runtimes versus Load

Models: 431A

1 78
Download 78 pages 27.75 Kb
Page 55
Image 55

UPS

Power

Input/

Output

Cables

4300 Series UPS

 

 

 

TB3

 

 

 

 

 

 

 

3

4

7

8

AC IN

TB1

 

 

 

AC OUT

U V W N N U V W +

 

 

 

431B

 

TB1

 

(Battery Shunt Trip

 

 

 

 

 

& Aux 1)

1

2

7

8

 

 

 

CB1 (DC Power)

+-

Figure 12-7 - 431B DC and Breaker Cable Connections

1.Run the pre-wired shunt trip cable shown in Figure 12.8 from the 431B through the 431B/UPS cable access port, Figure 12-5, and plug it into the corresponding MATE-N-LOK in the UPS.

2.Reinstall the dead fronts.

Figure 12-8 - 431B Factory Supplied

Shunt Trip Wiring

12.7431Bx000xxER111 Backup Runtime Tables

The following Table 12.4 gives the typical backup runtimes at various loads for a single cabinet 431Bx000xxER111.

Table 12.4 - 431B Typical Runtimes versus Load

UPS

Capacity

PF

 

 

 

Runtime in Minutes at % Full Load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100%

90%

80%

 

70%

60%

50%

40%

 

30%

20%

10%

4300

30kVA

0.8

17

21

24

 

30

38

45

59

 

>90

>90

>90

4300

30kVA

0.9

15

17

20

 

24

33

38

53

 

74

>90

>90

4300

50kVA

0.8

8

9

11

 

14

17

24

32

 

46

70

>90

4300

50kVA

0.9

7

8

9

 

11

15

20

26

 

44

60

>90

4300 Series Ancillary Cabinets Installation and Operation Manual

47

Page 55
Image 55
Toshiba 431A operation manual 12.7 431Bx000xxER111 Backup Runtime Tables, 431B Typical Runtimes versus Load