No.

Part

4Battery Retention Strap

5MCCB - Battery Cabinet Breaker

+MCCB Positive Lug, Battery Cabinet DC Out

MCCB Negative Lug, Battery Cabinet DC Out

6Access for Battery Cabi- net Output Lugs

7Anderson Connectors for Battery String Discon- nect (1 set per shelf)

(All cabinets are O’Brien Black (Textured))

5

7

+

6

4

Figure 12.2 Battery Cabinet MCCB Detail

12.1431B Estimated Runtimes

TABLE 12.1 431B ESTIMATED RUNTIMES

Battery Cabinet

UPS Rat-

DC Bus Nominal

Batteries/Circuit Breaker

Battery Runtime in Min.

Part Number*

ing

Voltage

Configuration

@ Full Load, 0.8 PF

431B30017ER111

30 kVA

288 VDC

1 Breaker, 1 Battery String

017

– 17 min. runtime

 

 

 

 

 

 

431B30008ER111

50 kVA

288 VDC

1 Breaker, 1 Battery String

008

– 8 min. runtime

12.2EQUIPMENT WARNING LABELS

DO NOT attempt to install, operate, maintain or dispose of this equipment until you have read and under- stood all of the product warnings and user directions that are contained in this instruction manual.

FIgure 12-2 shows examples of warning labels that may be found attached to the equipment. DO NOT remove or cover any of the labels. If the labels are damaged or if additional labels are required, contact your TOSHIBA representative for additional labels.

The following are examples of the warning labels that may be found on the equipment. The labels are there to provide useful information or to indicate an imminently hazardous situation that may result in seri- ous injury, severe property and equipment damage, or death if the instructions are not followed.

4300 Series Ancillary Cabinets Installation and Operation Manual

41

Page 49
Image 49
Toshiba 431A operation manual 12.1 431B Estimated Runtimes, Battery Cabinet Mccb Detail