TABLE 12.2 - 431B POWER CABLE SIZES

(Cable sizes for 75°C Copper Cable)

Recommended/Maximum Wire size and Torque Requirement

UPS

Maximum DC

Batt Cab

Recommended Cable

UPS Terminal

431B MCCB Lug

Rating

Current

MCCB

Sizes

Lug Tightening

Tightening

 

 

 

 

Torque

Torque

30 kVA

127 Adc

150 A

#1 AWG – 350 kcmil

200 lb-in

225 lb-in (25 N•M)

50 kVA

214 Adc

250 A

250 kcmil – 350 kcmil

200 lb-in

225 lb-in (25 N•M)

* Wire capacity for DC lugs is 350 kcmil - 6 AWG,

TABLE 12.3 - 431B MCCB CONNECTIONS

Battery Cab

MCCB

Lug Cable

Condutors

Strip

Lug Torque

Capacity

Rating

Capacity

per Lug

Length

 

30 kVA

150 A

#4 AWG - 4/0

1

1 in.

225 lb-in (25 N•M)

50 kVA

250 A

3/0 - 350 kcmil

1

1 in.

225 lb-in (25 N•M)

Go to Section 12.4

12.4Place the 431B Cabinet

The 431B Cabinet has four mounting holes to anchor the unit after is has been set in place. See Figure 12-4. Use 1/2 in (12 mm) bolts to anchor the 431B.

Verify the Left Side Access Plate of the 431B and the corresponding Right side ac- cess plate of the 4300 UPS are removed before anchoring the unit.

NOTE: Ensure the 431B can be joined to the UPS before final anchoring of the 431A. Use four 3/8 in. -16 x 2 in long bolts to bolt the ancillary cabinet frames together. See Section 12.5.

Figure 12-4 - 431B Base Anchor Points

4 x 0.63 in. Dia. (16 mm) Back

26.7 in..

(677 mm)

Front

19.0 in. (483 mm)

44

4300 Series Ancillary Cabinets Installation and Operation Manual

Page 52