TABLE 12.2 - 431B POWER CABLE SIZES
(Cable sizes for 75°C Copper Cable)
Recommended/Maximum Wire size and Torque Requirement
UPS | Maximum DC | Batt Cab | Recommended Cable | UPS Terminal | 431B MCCB Lug |
Rating | Current | MCCB | Sizes | Lug Tightening | Tightening |
|
|
|
| Torque | Torque |
30 kVA | 127 Adc | 150 A | #1 AWG – 350 kcmil | 200 | 225 |
50 kVA | 214 Adc | 250 A | 250 kcmil – 350 kcmil | 200 | 225 |
* Wire capacity for DC lugs is 350 kcmil - 6 AWG,
TABLE 12.3 - 431B MCCB CONNECTIONS
Battery Cab | MCCB | Lug Cable | Condutors | Strip | Lug Torque |
Capacity | Rating | Capacity | per Lug | Length |
|
30 kVA | 150 A | #4 AWG - 4/0 | 1 | 1 in. | 225 |
50 kVA | 250 A | 3/0 - 350 kcmil | 1 | 1 in. | 225 |
Go to Section 12.4
12.4Place the 431B Cabinet
The 431B Cabinet has four mounting holes to anchor the unit after is has been set in place. See Figure
Verify the Left Side Access Plate of the 431B and the corresponding Right side ac- cess plate of the 4300 UPS are removed before anchoring the unit.
NOTE: Ensure the 431B can be joined to the UPS before final anchoring of the 431A. Use four 3/8 in.
Figure 12-4 - 431B Base Anchor Points
4 x 0.63 in. Dia. (16 mm) Back
26.7 in..
(677 mm)
Front
19.0 in. (483 mm)