11.3INSTALLATION INSTRUCTIONS

DANGER: HAZARDOUS VOLTAGES MAY EXIST.

Verify all power is removed from the UPS and power cables prior connecting the power cables to the Battery Cabinet and UPS terminals.

The Toshiba Battery Cabinet (431B) comes in either of two configurations:

431B300006YR13x: Three battery strings, four battery trays per string, in the upper section,

431B500008YR162: Six battery strings, four battery trays per string, three strings each in the upper and lower sections.

NOTE: Battery trays are Toshiba P/N 60995.

No more than two Toshiba 431B Battery Cabinets may be connected in parallel to the 4300 Series UPS.

INSTRUCTIONS IMPORTANTES CONCERNANT LA SÉCURITÉ

CONSERVER CES INSTRUCTIONS

Cette notice contient des instructions importantes concernant la sécurté

ATTENTION ATTENTION

4431B and 4300 UPS

Un battery puet présenter un risque de choc électrique, de brûlure par transfert d’ énergie.

L’élimination des batteries est règlementèe. Consultar les codes locaux à cet effet

Select the proper cable size per Table 11.3.

Terminate the cable end connecting to the 431B with 0.5 inch bolt hole terminal lugs. See Table 11.2 below.

The 431B DC Output is equipped with terminal bus strips pre-drilled in a standard NEMA two-hole pattern (0.5 in. bolt holes on 1.75 in. centers) to facilitate installation of power cables. Use of NEMA two-hole cable terminations is recommended.

Table 11.1: Bolt Tightening Specifications

ITEM

Torque

 

Grade 8, 1/2 in. Bolts

119 ft-lb (161

N•M)

The following table lists examples of NEMA 2-hole compression type fittings.

Table 11.2: Compression Fittings

Ilsco P/N

Description

Conductor Size

Fitting Color

CLND-6-12-134

Long Barrel

#6

Blue

CSWD -6-12-134

Short Barrel

 

 

CLND-4-12-134

Long Barrel

#4

Grey

CSWD -4-12-134

Short Barrel

 

 

CLND-3-12-134

Long Barrel

#3

White

 

 

 

 

CLND-2-12-134

Long Barrel

#2

Brown

CSWD -2-12-134

Short Barrel

 

 

CLND-1-12-134

Long Barrel

#1

Green

CSWD -1-12-134

Short Barrel

 

 

CLND-1/0-12-134

Long Barrel

1/0

Pink

CSWD -1/0-12-134

Short Barrel

 

 

CLND-2/0-12-134

Long Barrel

2/0

Black

CSWD -2/0-12-134

Short Barrel

 

 

34

4300 Series Ancillary Cabinets Installation and Operation Manual

Page 42
Image 42
Toshiba 431A operation manual 4431B and 4300 UPS, Bolt Tightening Specifications Torque