12.5Join the Battery Cabinet with the UPS

The Toshiba Battery Cabinet (431B) is equipped with four (4) ea.14 mm mating holes located on the left and right sides of the cabinet vertical frame members.

1. Ensure Battery Cabinet Breaker are OFF.

WARNING

Switch the Battery Cabinet Circuit Breaker OFF Before Cabling the Battery Cabinet.

Failure to switch breakers off may result in electric shock, burns, personal injuries or UPS failure.

2.Remove the UPS dead-fronts.

3.Remove the cable access plate at the lower-front right side of the UPS Cabinet.

4.Remove the cable access plate at the lower-front left side of the 431B Cabinet. (See Figure 12-5)

5.Position the 431B cabinet to the right of, and adjacent to, the UPS Cabinet.

6.Align the four 14 mm bolt holes on the left side of the 431B Cabinet with the matching four 14 mm bolt holes on the right side of the UPS Cabinet.

7.Bolt the cabinets together with four 3/8-16 in. x 2 in. long bolts.

Figure 12-5 - 431B Cable

Access Plate

4300 Series Ancillary Cabinets Installation and Operation Manual

45

Page 53
Image 53
Toshiba 431A operation manual Join the Battery Cabinet with the UPS