13.7Join the 431A Cabinet with the 431M
The Toshiba Auxiliary Cabinet (431A) is equipped with four 14 mm mating holes located on the front and back of the left and right sides of the cabinet.
DANGER: HAZARDOUS VOLTAGES MAY EXIST.
Verify all power is removed from the UPS and power cables prior connecting the power cables to the Auxil- iary Cabinet terminals, Maintenance Bypass Switch terminals, or UPS terminals.
1.Remove the top and bottom 431M Front panels.
2.Remove the cable access plate at the
3.Remove the cable access plate at the
4.Position the 431A cabinet to the left of and adjacent to the 431M Cabinet.
5.Align the four 16 mm bolt holes on the right side of the 431A Cabinet with the matching four 16 mm bolt holes on the left side of the 431M Cabinet.
6.Bolt the cabinets together with four
7.Secure the 431A base anchor bolts.
8.Select the power cables per Tables
•Cable size for the UTILITY and LOAD terminals depend on the transformers Input/Output Voltages.
•The UPS Input/Output cables will be the same size: 3Phase /4Wire 208/120V.
9.Run power cables from 431M bus stub terminals UTILITY IN to 431A TB1 - UPS IN terminals. (Fig.
10.Run power cables from 431M bus stub terminals LOAD IN to 431A TB2 - UPS OUT terminals. (Fig.
11.Run the appropriately sized power cables from 431A TB1 to the 431M From UTILITY (Figure
12.Connect 431M UPS IN Bus Terminals (Figure
13.Connect 431M UPS OUT Bus Termnals (Figure
14.Connect the Neutral cables to the 431M Neutral Bus stub, Figure
15.Connect the Mechanical Interlock Solenoid power plug, TB1
16.Connect the Ground wires (#2 AWG or better) to the ground bus, Figure
17.Verify the connections are correct.
18.Install the 431M top and bottom Dead Fronts.
Utility Power
L1
L2
L3
N
1
431A
TB1
(From Utility) (To UPS IN)
H1 H2 H3 N N L1 L2 L3
(Optional)
TB2
(From UPS OUT) (To LOAD)
H1 H2 H3 N N L1 L2 L3
(Optional) N
L1
L2
L3
Critical Load
431M
A |
| UPSIN | A | |
C UTILITYIN | C | |||
B |
|
| B | |
A | LOADIN | OUTUPS | A | |
B | B | |||
|
| |||
C |
|
| C |
NEUTRAL
N N N N
TB1
1 2 3 4 5 6 7 8
P1 J1 |
4300 Series
UPS
|
|
|
|
|
|
|
| H1 | IN) |
|
|
| |
| H2 |
|
| |||
| (UPS |
|
|
| ||
| H3 |
|
|
|
| |
| N |
| TB1 | |||
|
|
|
| |||
|
|
| OUT) |
|
|
|
| N |
|
|
| ||
| L1 |
|
| |||
| L2 | (UPS |
|
|
| |
| L3 |
|
| |||
| + |
|
| 24V DC | ||
| - |
|
| |||
|
|
|
| PCB | ||
|
|
|
| |||
|
|
|
| |||
11- |
|
| ||||
|
|
|
| |||
|
|
|
Figure 13-7 - Power Cabling Between Auxiliary Cabinet, MBS, and UPS
58 | 4300 Series Ancillary Cabinets Installation and Operation Manual |