FILE NO. SVM-10020

Item

Operation flow and applicable data, etc.

Description

3.Outdoor fan The blowing air volume at the outdoor unit side is controlled. 1) The operation command sent

motor control Receiving the operation command from the controller of

from the remote controller is

 

indoor unit, the controller of outdoor unit controls fan speed.

processed by the indoor unit

 

* For the fan motor, a DC motor with non-stage variable

controller and transferred to the

 

controller of the outdoor unit.

 

speed system is used. However, it is limited to 8 stages for

 

2) When strong wind blows at

 

reasons of controlling.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

outdoor side, the operation of air

 

 

 

 

 

 

 

 

 

 

conditioner continues with the

 

 

 

 

 

 

 

 

 

 

fan motor stopped.

 

Air conditioner ON

 

 

 

 

 

 

 

 

 

 

 

 

 

3) Whether the fan is locked or not

 

(Remote controller)

 

 

 

 

 

 

 

 

 

 

 

 

 

is detected, and the operation of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

air conditioner stops and an

 

Indoor unit controller

 

 

 

 

 

 

alarm is displayed if the fan is

 

 

 

 

 

 

 

locked.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4) According to each operation

 

1) Outdoor unit

 

 

 

 

 

 

mode, by the conditions of

 

 

 

 

 

 

 

outdoor temperature (To) and

 

operation command

 

 

 

 

 

 

 

(Outdoor fan control)

 

 

 

 

 

 

compressor revolution, the speed

 

 

 

 

 

 

 

 

 

 

of the outdoor fan shown in the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

table is selected.

 

2) Fan speed 400.

YES

Fan motor OFF continues

 

 

 

 

 

 

when the motor OFF.

(Use wind for heat

 

 

 

 

 

 

 

 

 

(by strong wind)

 

exchanging)

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan motor ON

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3) Fan lock

 

Air conditioner

 

Alarm

 

 

 

 

 

OFF

 

display

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4) Motor operates as shown in the table below.

In cooling operation

Compressor speed (rps)

< 22.1

< 50.3

50.3

<

MIN

MAX

MIN

MAX

MIN

MAX

 

 

 

To 100°F (38°C)

f 6

f 9

f 8

f B

f A

 

f E

 

To 82°F (28°C)

f 5

f 9

f 7

f B

f 9

 

f E

To

To 59°F (15°C)

f 3

f 7

f 5

f 9

f 7

 

f B

To 42°F (5.5°C)

f 1

f 3

f 1

f 7

f 3

 

f 9

 

 

 

To 32°F (0°C)

f 1

f 3

f 1

f 5

f 3

 

f 7

 

To 22°F (-5°C)

f 0

f 1

f 0

f 3

f 1

 

f 4

 

To 100°F (38°C)

f 6

f 9

f 8

f B

f A

 

f B

During ECO,

To 82°F (28°C)

f 5

f 9

f 7

f B

f 9

 

f B

To 59°F (15°C)

f 3

f 7

f 5

f 9

f 7

 

f B

QUIET and

 

 

 

 

 

 

 

 

To 42°F (5.5°C)

f 1

f 3

f 1

f 7

f 3

 

f 9

comfort sleep

 

To 32°F (0°C)

f 1

f 3

f 1

f 5

f 3

 

f 7

 

 

 

To 22°F (-5°C)

f 0

f 1

f 0

f 3

f 1

 

f 4

When To is abnormal

f 1

f F

f 1

f F

f 1

 

f F

 

 

 

 

 

 

 

 

 

In Heating operation

Compressor speed (rps)

< 30.5

< 55.1

55.1 <

 

To 50°F (10°C)

f 6

f 8

f 9

To

To 42°F (5.5°C)

f 8

f A

f C

To 22°F (-5°C)

f A

f B

f D

 

 

To < 22°F (-5°C)

f A

f B

f D

 

To 50°F (10°C)

f 5

f 7

f 9

During

To 42°F (5.5°C)

f 7

f 9

f B

ECO mode

To 22°F (-5°C)

f 9

f A

f B

 

To < 22°F (-5°C)

f 9

f A

f B

When To is abnormal

f D

f D

f D

 

 

 

 

 

Outdoor fan speed (rpm)

Tap

RAS-15LAV-UL

RAS-17LAV-UL

RAS-22LAV-UL

f 0

0

0

0

f 1

230

230

230

f 2

300

300

300

f 3

350

350

350

f 4

410

410

410

f 5

480

480

480

f 6

500

500

500

f 7

530

530

530

Tap

RAS-15LAV-UL

RAS-17LAV-UL

RAS-22LAV-UL

f 8

560

560

560

f 9

640

640

640

f A

670

670

670

f B

700

700

750

f C

800

800

920

f D

800

800

920

f E

900

1000

1000

f F

900

1000

1000

– 32 –