FILE NO.
PPressure measurement
Gauge attaching port
Vacuum pump connecting port
Deoxidized copper pipe
Outer dia. : 1/2 in. (12.7mm)
Thickness : 1/32 in (0.8mm)
Muffler
INDOOR UNIT | T1 | Temp. measurement |
|
| |
Indoor heat |
|
|
exchanger |
|
|
| TC | ) |
| Allowableheight difference:33ft (10m Allowablepipe length | |
Sectional shape | TA | |
Cross flow fan |
| |
Deoxidized copper pipe |
|
|
Outer dia. : 1/4 in. (6.35mm) |
| |
Thickness : 1/32 in (0.8mm) |
| |
of heat insulator |
|
|
|
| Strainer |
Muffler
Max. : 66ft (20m)
Min. : 6.6ft (2m)
Chargeless : 50ft (15m)
Charge : 0.22oz/ft (20g/m) (51 to 66ft)
Muffler
High pressure SW
TD
Accumulater tank
Compressor
TS
Fusible Plug | TO |
| |
Outdoor heat | Split capillary |
exchanger | |
| Distributor |
| TE |
Propeller fan
OUTDOOR UNIT
Pulse Modulating valve at liquid side
Refrigerant amount: 3.09 lbs (1.40kg)
NOTE: Gas leak check position
Refrigerant flow (Cooling) Refrigerant flow (Heating)
NOTE :
•The maximum pipe length of this air conditioner is 66 ft (20m). When the pipe length exceeds 50 ft (15m), the additional charging of refrigerant, 0.22 oz/ft (20g per 1m) for the part of pipe exceeded 50 ft (15m) is required.
[Max. 0.22 lbs (100g)].
– 22 –