11-5-2. Wiring Failure (Interconnecting and Serial Signal Wire)
(1)Outdoor unit does not operate1)Is the voltage between L1 and S of the indoor terminal block varied?
Confirm that transmission from indoor unit to outdoor unit is correctly performed based upon the follow- ing diagram.
NOTE:•Measurement should be performed 2 minutes and 30 seconds after starting of the operation.
•Be sure to prepare a diode for judgment.
Terminal block at indoor side |
| ||
Red | S | S5277G | S5277G or equivalent |
White | L1 | (Diode with rated voltage of 400V | |
| or more is acceptable.) | ||
| L2 | Terminal block | Tester |
Normal time | : Voltage swings between DC15 and 60V. ................... | Inverter Assembly check |
Abnormal time | : Voltage does not vary. |
|
1)The outdoor unit stops 10 to 20 minutes after operation started, and 10 minutes or more are required to restart the unit.
Gas circulation amount is down. |
|
| Gas shortage | |
|
| |||
|
|
|
| Gas leak |
|
|
|
| |
|
|
|
| |
|
|
|
| |
Measure gas | pressure. |
| Pipe clogging | |
| ||||
|
|
|
| |
Thermo. operation of compressor |
|
|
2)If the unit stops once, it does not operate until the power will be turned on again.
To item of Outdoor unit does not operate.
3)The outdoor unit stops 10 minutes to 1 hour after operation started, and an alarm is displayed. (Discharge temp. error check code 03, 1E Sensor temp. error check code 02, 1C)
Gas leak
P.M.V. is defective.
Refer to the chart in
Miswiring of connecting wires of indoor/outdoor units
Clogging of pipe and