FILE NO. SVM-10020

 

 

 

Item

Operation flow and applicable data, etc.

Description

 

 

 

8. Louver control

This function controls the air direction of the indoor unit.

 

1) Louver

The position is automatically controlled according to the operation

 

position

mode (COOL/HEAT).

 

 

The set louver position is stored in memory by the microcomputer,

 

and the louver returns to the stored position when the next operation is performed. (Cooling/Heating memory position)

The angle of the louver is indicated as the louver closes fully is 0°.

1) Louver position in cooling operation

Cooling operation/AUTO (COOL)

Initial setting of "Cooling storage position"

Louver : Horizontal blowing (37.4°)

2) Louver position in heating operationHeating operation/AUTO (HEAT)

Initial setting of “Heating storage position”

Louver : Directs downward (76.9˚)

2) Air direction adjustment

 

 

 

 

 

 

 

 

 

 

 

The louver position can

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

be arbitrarily set up by

 

 

 

 

 

 

 

 

 

Air direction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressing [FIX] button.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Horizontal

 

 

Inclined

 

Blowing

 

Inclined

 

 

Horizontal

 

 

 

 

 

 

blowing

 

 

blowing

 

downward

 

blowing

 

 

blowing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3) Swing

Swing operation is perfor in range 35° with the Fixed position as

Swing

 

the center.

 

 

 

 

When pressing

 

If the swing range exceeded either upper or lower limit position,

[SWING] button during

 

swing operation is performed in range 35° from the limit.

operation, the louver

 

 

 

 

 

 

starts swinging.

 

Upper Limit

 

Upper Limit

5o

 

 

Position.

 

Position.

 

 

 

17.5o

 

 

 

 

 

Fixed

 

30o

 

 

Swing

 

 

 

 

17.5o

Position

 

 

 

 

range 35o

before start

 

 

 

 

 

 

swing

 

 

 

 

Fixed Position

Lower Limit

Swing

o

Lower Limit

 

 

range 35

Position

 

 

before start

Position.

 

 

 

swing.

 

 

 

 

 

 

 

 

 

 

 

 

– 36 –