| FILE NO. |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| Block distinction |
|
|
|
|
| Operation of diagnosis function |
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Check | Block |
| Check |
|
|
|
|
|
| Air | Display flashing | Action and Judgment | ||||
|
| Cause of operation |
|
|
| conditioner |
| |||||||||
code |
|
| code |
|
|
|
| error |
| |||||||
|
|
|
|
|
|
|
|
| status |
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Serial signal |
|
|
|
| 1) Defective wiring of the |
|
|
|
| Indoor unit | Flashes when | 1) to 3) The outdoor unit never | ||
|
| and connecting |
|
|
|
|
| connecting cable or |
|
|
|
| operates | error is detected. | operate. | |
|
| cable. |
|
|
|
|
|
|
|
|
| continue. | Flashing stop | Check connecting cable and correct | ||
|
|
|
|
|
|
| 2) Operation signal has not |
|
|
|
| Outdoor unit | and outdoor unit | if defective wiring. | ||
|
|
|
|
|
|
|
| send from the indoor unit |
|
|
|
| stop. | start to operate | Check 25A fuse of inverter P.C. board. | |
|
|
|
|
|
|
|
| when operation start. |
|
|
|
|
|
| when the return | Check 3.15A fuse of inverter |
|
|
|
|
|
|
| 3) Outdoor unit has not |
|
|
|
|
|
| signal from the | P.C. board. | |
|
|
|
|
|
|
|
| send return signal to the |
|
|
|
|
|
| outdoor unit is | Check operation signal of the indoor |
|
|
|
|
|
|
|
| indoor unit when operation |
|
|
|
|
| normal. | unit by using diode. Measure voltage | |
|
|
|
|
|
|
|
| started. |
|
|
|
|
|
|
| at terminal block of the indoor unit |
|
|
|
|
|
|
| 4) Return signal from the |
|
|
|
|
|
|
| between No.2 and No.3 (or L2 and S) | |
|
|
|
|
|
|
|
| outdoor unit is stop during |
|
|
|
|
|
|
| If signal is varied |
|
|
|
|
|
|
|
| operation. |
|
|
|
|
|
|
| replace inverter P.C. board. |
|
|
|
|
|
|
|
| Some protector |
|
|
|
|
|
|
| If signal is not varied, replace indoor |
|
|
|
|
|
|
|
| (hardware, if exist) of the |
|
|
|
|
|
|
| P.C. board. |
|
|
|
|
|
|
|
| outdoor unit open |
|
|
|
|
|
|
| 4) The outdoor unit abnormal stop at |
|
|
|
|
|
|
|
| circuit of signal. |
|
|
|
|
|
|
| some time. |
|
|
|
|
|
|
|
| Signal circuit of indoor |
|
|
|
|
|
|
| If the other check codes are found |
|
|
|
|
|
|
|
| P.C. board or outdoor |
|
|
|
|
|
|
| concurrently, check them together. |
|
|
|
|
|
|
|
| P.C. board is failure |
|
|
|
|
|
|
| Check protector (hardware) such |
|
|
|
|
|
|
|
| in some period. |
|
|
|
|
|
|
| as |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Check refrigerant amount or any |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| possibility case which may caused |
Note : Operation signal of the indoor unit shall be measured in the sending period as | high temperature or high pressure. | |||||||||||||||
picture below. |
|
|
|
|
|
|
|
|
|
|
|
| Check operation signal of the indoor | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Sending signal of the indoor unit when have not return |
| unit by using diode. Measure voltage | ||||||||||||
|
|
|
| |||||||||||||
| VDC |
|
| signal from the outdoor unit. |
| at terminal block of the indoor unit | ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| between No.2 and No.3 (or L2 and S) | |||
diode |
|
|
|
|
|
|
|
|
|
| *** |
|
| |||
60 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| If signal is varied | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
apply |
|
|
|
|
|
|
|
|
|
|
|
|
|
| replace inverter P.C. board. | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| If signal is not varied, replace indoor | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
by |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| P.C. board. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
voltage |
| 3 minutes Delay, start |
|
|
| 3 minutes stop |
|
|
|
|
|
|
|
| ||
|
|
| * |
|
| ** |
|
|
|
|
| |||||
|
| counting from power |
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
signal |
| supply ON or remote |
|
|
|
| Voltage variation stop |
|
|
|
|
|
|
|
| |
| OFF. |
|
|
|
| output. |
|
|
|
|
|
|
|
| ||
Measured |
|
|
|
|
|
|
| or have not voltage |
|
|
|
|
|
|
|
|
15 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 0 |
|
|
| 3 |
| 4 | 7 | 8 |
| Time (Min) |
| ||||
|
|
|
|
|
|
|
|
*Signal send only 1 minute and stop. Because of return signal from outdoor unit has not received. ** Signal resend again after 3 minutes stop. And the signal will send continuously.
*** 1 minute after resending, the indoor unit display flashes error.
– 72 –