| To | From | Expected Resistance |
|
|
|
|
Primary | Black | White (240 VAC Input) | 28.1 W |
|
|
|
|
| Black | Blue (240 VAC Input) | 53.1 W |
|
|
|
|
| Black | Red (240 VAC Input) | 62.4 W |
|
|
|
|
Secondary | Yellow | Yellow | 0.80 W |
|
|
|
|
Figure 33: Burner Transformer Ohm Chart
Combustion Blower
The combustion blower is a 3000 RPM, 208- 240 VAC, 0.33 A, 50/60 hz, blower motor. The winding resistance is 92 W. The combus- tion blower receives line voltage
Testing Procedure
1.Disconnect line voltage from the unit.
2.Take a resistance reading of the winding; resistance should be 92 W. If resistance is incorrect, the combustion blower is damaged or defective and must be replaced (page
3.Apply line voltage to the unit and check for line voltage
4.If no voltage is present, inspect the wire harness for damage or shorts (page 45).
5.If the wire harness is intact and undamaged, the combustion blower is damaged or defective and must be replaced (page
Modulating Gas Valve
The modulating gas valve is a combination gas valve with a 24 VAC primary solenoid valve and
valve has an adjustment shaft that adjusts the high and low flame pressure.
Testing Procedure
NOTE: See page 3 for instructions on adjusting the high and low flame gas pressure.
1.Disconnect line voltage from the unit.
2.Take a resistance reading of both coils, resistances should be 535k W and 44 W. If resistance is incorrect, the gas valve is damaged or defective and must be replaced (page
3.During warmup and cook mode, apply line voltage to the unit and check for 24 VAC at the primary solenoid coil and
4.If no voltage is present, inspect the wire harness for damage or shorts (page 45).
5.Check for 24 VAC leaving the ignition module (see Figure 35, page 28)
6.If wire harness is intact and undamaged, the modulating gas valve is damaged or defective and must be replaced (Pipe and valve assembly, page
Ignition Module
The ignition module generates 30,000 V at the spark igniter stud for direct ignition of the main burner when 24 VAC is applied. The module senses the presence of the burner flame and discontinues the ignition spark.
If the burner fails to ignite within 6 seconds, the module goes into safety lockout. If the burner does not maintain 1.5 DC uA mini- mum, the timed trial for ignition (6 seconds) is repeated and safety lockout occurs. If safety lockout occurs, power must be removed from the module before it can be restarted.
Testing Procedure
NOTE: The ignition module is different in domestic and international model ovens. Figure 34 shows the differences in the terminal labels between the two models.
27
OVEN SYSTEMS