2 2 OVEN SYSTEMS
b) If terminal resistance is incorrect, | Testing Procedure | |
replace the power supply. | 1. Disconnect line voltage to the unit. | |
| ||
3. If correct voltage is present, disconnect the | 2. Take a resistance reading of the coil. | |
output wires and check output | ||
3. If coil resistance is correct (577 W): | ||
+OUT) for 24 VDC. | ||
4. If voltage is present with output wires | a) Apply line voltage to the unit. | |
b) Check for 24 VDC at the coil of the | ||
disconnected and not present when the | ||
wires are connected, inspect the wire | relay when the unit is calling for heat. | |
harness for damage or shorts. | c) Check the state of the contacts. | |
5. If the wire harness is intact and undamaged, | ||
the power supply is damaged or defective | ||
and must be replaced (page | ||
| ||
Power Supply - 24VDC (International) | ||
| ||
The power supply - 24VDC (international) | ||
converts line voltage to 24 VDC. Line voltage is | ||
connected to terminals L & N. The output (24 | ||
VDC) is on terminals | 4. If the coil resistance is incorrect, replace the | |
| ||
Testing Procedure | K3 relay. | |
| ||
1. Check for line voltage | K4 Relay - Ignition | |
terminals L & N. | ||
The K4 relay is a single pole, double throw | ||
2. If correct voltage is present, check output | ||
relay with a 24 VAC coil. The coil resistance is | ||
585 k W and the contact rating is 20 A at 240 | ||
disconnected). | VAC. When 24 VAC is applied to the coil, the | |
3. If voltage is present with output wires | normally open contacts (7 & 4 or C & NO) | |
close and the normally closed contacts (7 & 1 | ||
disconnected and not present when the | ||
or C & NC) open. | ||
wires are connected, inspect the wire | ||
| ||
harness for damage or shorts (page 45). | The K4 relay uses the normally closed contacts. | |
| ||
4. If wire harness is intact and undamaged, | If 24 VAC is applied to the ignition module | |
and 1.5 uA minimum is not maintained, the | ||
the power supply - 24VDC (international) | ||
ignition module applies 24 VAC to the relay | ||
is damaged or defective and must be | ||
and the contacts open. When the contacts open | ||
replaced (page | ||
the I/O control board shows an “F3 No Flame” | ||
| ||
K3 Relay - Gas | fault. | |
|
The K3 relay is a single pole, double throw relay with a 24 VDC coil. The coil resistance is 577 W and the contact rating is 20A at 240 VAC. When 24 VDC is applied to the coil, the normally open contacts (7 & 4 or C & NO) close applying line voltage to the burner trans- former and the combustion blower.
Testing Procedure
1.Disconnect line voltage to the unit.
2.Take a resistance reading of the K4 coil.