Ic Prepare boiler location — clearances

GOLD GV Water boiler series 3 — manual

Ic Prepare boiler location — clearances

Clearance options:

Large space

The boiler space must be at least as big as shown in Figure 1 to qualify as a large space.

Air openings to a large space can be per manual Section Ie.

The space will probably be large enough for most service and maintenance to be done in place.

Small space

You can install the boiler in a space smaller than Figure 1, but no smaller than shown in Figure 2 — this is called a small space installation.

Air openings to a small space must provide at least 1 square inch free area for every 1,000 Btuh of boiler input (at least 75 sq. in. for GV-3, 105 sq. in. for GV- 4, 140 sq. in. for GV-5 or 175 sq. in. for GV-6). The air opening free area must be at least this size even if the boiler uses outside air.

Air openings have to be within 6 inches of the floor and 6 inches of the ceiling of the space to prevent overheating of boiler internal components.

Provide at least screwdriver clearance to jacket front panel screws for removal of front panel for inspection and minor service.

The boiler cannot be serviced in place. Pipe the boiler with unions and isolation valves so it can be slid out of the space and serviced in an adjacent area. The space has to be equipped with a door so boiler can be accessed, unpiped and removed.

No other appliance or air handler can be installed in the same space or share its air supply.

Install the boiler so control system components are protected from

dripping or spraying water or

rain during operation. Allowing these components to become wet could cause a boiler failure, resulting in severe personal injury, death or substantial property damage.

Figure 1

Large space — minimum clearances between boiler and walls or obstructions as below; see Section Ie for minimum combustion/ventilation air opening sizing.

TOP VIEW

 

 

Wall

 

 

 

6"

 

 

 

min

 

Wall

36"

6"

Wall

min

min

 

 

Boiler

 

 

 

front

 

 

 

36"

 

 

 

min

 

Wall or obstruction

85006a

FRONT VIEW

 

Ceiling

 

 

36"

 

 

min

 

Wall

 

Wall

36"

Boiler

6"

min

min

 

front

 

 

Floor

 

10

Part number 550-141-850/0699