•Installation •
Annual start-up — inspect
Water piping
1.Check the boiler interior piping and all system piping for signs of leaks.
2.Repair any leaks before proceeding.
Eliminate all system leaks. Continual fresh makeup water will reduce boiler life. Minerals can build up in sections, reducing heat transfer, overheating cast iron, and causing section failure.
Do not use
Condensate drain system
1.Inspect the condensate trap hose for deterioration.
2.Check for any obstructions in the trap hose by squeezing the tubing.
3.If there is any doubt the condensate drain system is flowing freely, remove the clamp and hose from the bottom of the vent starter tee. Slide a funnel outlet into the trap hose and pour water through. It should exit at the termination of the condensate drain line.
4.If the owner’s monthly inspection of the condensate drain system has indicated a tendency for the trap to run dry, install a condensate drain line check valve kit, available through your
Annual start-up — service
Blower motor (Figure 27)
1.With boiler power OFF, place a few drops of S.A.E. 20 motor oil in each of the two oil cups.
Use only S.A.E. 20 motor oil to lubricate the blower motor. Do not use universal household oils. Motor could be damaged, resulting in possible severe property damage.
Oiled-bearing circulators
1.Both of the circulators installed in the boiler are water- lubricated. No oiling is required.
2.Check other circulators in the system. Oil any circulators requiring oil, following circulator manufacturer’s instructions.
Figure 27 Blower motor
Oil cup
Oil cup
85037
Annual | |
| 1. Follow the instructions in manual Section VII. |
2.Verify cold fill pressure is correct and that fill system is working properly.
3.Verify antifreeze level (if used) is at the right concentration and that inhibitor level is correct.
4.Check gas piping, per manual Sections V and VIb, verifying no indications of leakage and all piping and connections are in good condition.
5.Read the Lighting instructions (Figure 25 or 26 of this manual or on boiler label) applying to the boiler (ensuring the instruction applies to the gas valve installed in the boiler).
6.Start the boiler following the Lighting instructions and manual Section VIId.
Part number | 59 |