Capacity of pipe for pipe size of:

• Installation • Start-Up • Parts • Maintenance

Always use a wrench on the manifold to

Figure 17

Gas supply connection to GV

prevent it from twisting when installing or

 

boiler gas manifold

removing external gas piping. Failure to do

 

 

so could damage the blower housing

 

 

assembly, resulting in a leakage of

 

 

Service valve

(by others)

Ground joint union

(by others)

½" NPT

Blower housing cover

Manifold

Gas valve

Drip leg (by others)

Nipple length must provide at least 3 inches between the cap and tee, per ANSI Z223.1.

Outlet hex fitting

85031

Gas valve outlet hex fitting is a LEFT- HAND thread.

Gas pipe

 

Capacity of pipe for pipe size of:

 

 

Table 3

Pipe capacity for 0.60 specific

length

 

(Capacity in cubic feet gas per hour)

 

 

 

gravity natural gas

(feet)

½"

 

¾"

1"

1¼"

 

1½"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

132

 

278

520

1050

 

1600

 

 

 

20

92

 

190

350

730

 

1100

 

 

 

30

73

 

152

285

590

 

860

 

 

 

40

63

 

130

245

500

 

760

 

 

 

50

56

 

115

215

440

 

670

 

 

 

75

45

 

93

175

360

 

545

 

 

 

100

38

 

79

150

305

 

460

 

 

 

150

31

 

64

120

250

 

380

 

 

 