• Installation •
CHART 2 — TSTAT CIRC & POWER lights flashing
Electrical shock hazard — Wherever you see ▲ TURN OFF POWER▲ , follow the instructions. Failure to follow instructions could result in severe personl injury, death or substantial property damage.
Is return water temperature sensor clamped securely to the return pipe in the boiler?
Yes | No | |
|
|
|
•Attach sensor to pipe with clamp provided.
•If problem persists, replace return water temperature sensor.
•Retest.
• Check for stray voltage on the incoming thermostat wires. | does occur under any condition, check and correct the |
Disconnect the two external wires connected to the boiler | external wiring. (This is a common problem when using |
thermostat wires. | zone valves.) |
• Connect a voltmeter across the two incoming wires. Close • | Once the external thermostat circuit wiring is checked and |
each thermostat, zone valve and relay in the external circuit | corrected if necessary, reconnect the external thermostat |
one at a time and check the voltmeter reading across the | circuit wires to the boiler thermostat wires and allow the boiler |
wires. There should NEVER be a voltage reading. If a voltage | to cycle. |
Did you find and correct a voltage across the two external thermostat circuit wires?
Yes
No
•Boiler should now operate per the normal sequence of operation shown in Figure 22 if wiring was corrected.
•Remove CIRCULATORS plug (Figure 34, Item 4) from plug receptacle of control module.
•Place voltmeter leads across the
Does the voltmeter indicate 120 VAC?
No | Yes | ||
|
|
|
|
Is boiler internal Bypass circulator operating?
No | Yes | |
|
|
|
• Check the boiler internal return pipe where it enters the boiler sections. The TSTAT CIRC and POWER lights will flash as long as the return water temperature is less than
130 ˚F. |
• Wait up to 20 minutes to give the boiler and system a |
chance to respond. |
Does problem persist? |
•Replace GCM (control module).
•Retest.
•Replace circulator harness.
•Retest.
•Test wire continuity of circulator wire harness.
Is harness ok?
| No | Yes | ||
|
|
|
|
|
|
|
|
|
|
No | Yes | |
|
|
|
• Boiler may now be operating |
normally. Verify against |
Figure 22, sequence of |
operation. |
•Reconnect circulator harness to GCM.
•Attempt to get the circulator started by giving it a sharp rap on the end of the circulator motor (to release a possibly locked impeller).
•If the circulator begins to operate, allow it to operate for a few minutes to see if the problem clears.
•If problem persists, replace the Bypass circulator.
•Retest.
• If boiler appears not to be heating, troubleshoot boiler per |
CHART 8 (no heat problems). If problem cannot be |
resolved, replace water temperature sensor and retest. |
Then replace GCM (control module) if sensor does not |
correct the problem. |
• If boiler is heating, but the temperature at the return pipe |
does not increase above 130 ˚F, there may be an |
the boiler. Check external piping and correct. |
Part number | 75 |