CHART 4 PRES SWITCH & POWER lights flashing

Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.

Reset boiler control by turning off power at service switch or turning down thermostat for at least 45 seconds.

Thermostat should call for heat and appropriate zone valves open.

Does blower motor operate?

No

Yes

Wait 45 seconds.

Does blower motor operate?

No

Yes

 

 

 

Is blower wheel turning at speed of blower motor?

No

Yes

 

 

Remove BLOWER plug (Figure 34, Item 3) from plug receptacle of control module.

Place voltmeter leads across the 120 VAC N and 120 VAC H pins of the BLOWER receptacle.

Does the voltmeter indicate 120 VAC?

No

Yes

 

 

 

TURN OFF POWERat service switch.

Does blower wheel turn freely by hand?

No

Yes

 

 

TURN OFF POWERat service switch.

Properly position blower wheel on blower motor shaft and tighten set screw. (Or replace blower housing assembly.)

Retest.

Wait 5 minutes.

Is purge light flashing?

No

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

Properly position

 

 

 

 

 

 

blower wheel on

 

Replace blower

blower motor shaft

 

motor. (Also check

and tighten set screw.

 

blower housing

(Or replace blower

 

assembly. Replace if

housing assembly.)

 

necessary.)

Retest.

 

Retest.

 

 

 

 

 

Remove one of the red wires connected to the pressure switch.

Check continuity across the switch terminals.

Does the ohmmeter indicate the switch is closed?

No

Yes

 

 

 

 

Boiler should be in normal operating sequence.

Observe operation until thermostat is satisfied and blower has completed its post- purge cycle.

Check condensate trap. Is there condensate present?

 

No

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are vent or combustion air

 

Drain condensate.

 

Retest.

passages blocked?

 

 

 

 

 

 

 

 

 

 

 

 

No

 

Yes

 

 

 

 

 

 

 

 

 

 

 

Replace control module. Retest.

Check air pressure switch per manual Section XI. Replace if necessary. Retest.

Clear passages and recycle boiler. Recheck boiler operation.