GOLD GV Water boiler series 3 — manual

XIc Troubleshooting — air pressure switch

Checking the air pressure switch

Do not use manometer as shown in Figure 33 to test gas valve outlet pressure. Where instructed in this manual to check gas valve outlet pressure, follow instructions carefully, particularly regarding connection of manometer. Manometer fluid will cause permanent damage to gas valve. Severe personal injury, death or substantial property damage can result.

Check switch pressure setting

Figure 33 Connecting a manometer to

1.

See Figure 33.

check air pressure switch. DO

NOT use this arrangement to

 

 

2.

Remove both air pressure switch hoses from air

check gas valve.

pressure switch.

3.Install tees and tubing as shown in Figure 33 to inclined manometer.

4.

Turn off gas valve and set thermostat to call for heat.

Suction

Pressure

 

Blower will run but burner will not ignite.

 

 

5.

Check for 24 VAC between both air pressure switch

 

 

 

terminals and ground.

 

 

6.

If manometer reading is at least 1.4" w.c., but there is

Inclined tube

 

 

not 24 VAC between both air pressure switch

manometer

 

 

terminals and ground, replace air pressure switch.

 

 

Troubleshooting air pressure reading

1.If manometer reading is lower than 1.4" w.c. check for possible causes:

blockage in hoses.

loose blower wheel on motor shaft.

blower motor not at proper rpm.

blockage in air inlet or hose.

blockage in flue pipe or termination.

condensate trap filled w/condensate.

Return to normal operation

1.When pressure reading is proper and air pressure switch is operating properly, remove tees and reinstall hoses to air pressure switch.

Red

White

Shown with Robertshaw 7200DERN gas control

85027

68

Part number 550-141-850/0699

Page 68
Image 68
Weil-McLain GOLD DV WATER BOILER manual XIc Troubleshooting air pressure switch, Checking the air pressure switch