XIg Troubleshooting — GCM lights

GOLD GV Water boiler series 3 — manual

XIg Troubleshooting — GCM lights

CHART 1 — Troubleshooting POWER light status

Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personal injury, death or substantial property damage.

 

 

 

Is POWER light off?

 

 

 

 

 

 

 

• Make sure service switch or circuit breaker is on or fuses

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

are good.

 

 

 

 

 

No

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Remove 120 VAC IN plug (Figure 34, Item 1) on control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

module.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Using voltmeter, check across top and bottom pins of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is POWER light...

 

 

 

 

 

 

 

120 VAC IN receptacle.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Does voltmeter indicate 120 VAC?

 

 

Flashing

Flashing with

 

On steady

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

alone
another light

 

(not flashing)

 

 

 

 

No

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TSTAT CIRC

 

Chart 2

 

Chart 6

 

 

 

 

Problem is with incoming

 

 

 

 

 

light flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

electricity. Have licensed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LIMIT

 

Chart 3

 

Chart 7

 

 

 

 

electrician repair circuit.

 

 

 

 

 

light flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRES SWITCH

 

Chart 4

 

 

 

 

 

 

 

• Reconnect 120 VAC IN plug.

 

 

light flashing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Remove 120 VAC transformer PRIMARY plug (Figure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLAME

 

Chart 5

 

 

 

 

 

 

 

34, Item 2) on control module.

 

 

light flashing

 

 

 

 

 

 

 

 

• Using voltmeter, check across top and bottom pins of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRIMARY receptacle.

 

 

 

 

 

For insufficient heat or no heat problem, go to

 

 

 

 

 

 

 

 

 

 

 

 

 

Does voltmeter indicate 120 VAC?

 

 

Chart 8 if POWER light is on steady, with no other

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

light flashing.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Usually indicates polarity on incoming 120 VAC power

 

 

 

 

 

 

 

 

 

Replace control module.

 

 

 

line is wrong.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Retest.

 

 

 

TURN OFF POWERat service switch or breaker,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

then reverse the HOT and NEUTRAL wires entering the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

boiler in the J-box.

 

 

 

 

 

 

 

 

 

 

• Reinstall 120 VAC transformer PRIMARY plug.
• Restore POWER at service switch or breaker.

 

 

 

 

 

 

 

 

• Remove 24 VAC transformer plug (Figure 34, Item 7) on

 

 

 

Is POWER light flashing now?

 

 

 

 

 

 

 

 

 

 

 

control module.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Using voltmeter, check across pins of receptacle.

 

 

No

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

Does voltmeter indicate 24 VAC?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Have system checked by a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

licensed electrician.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If problem persists, call your

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boiler should now

 

 

local Weil-McLain sales

 

 

 

 

Replace transformer.

 

Replace control module.

operate normally.

 

 

representative.

 

 

 

 

Retest.

 

Retest.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

74

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Part number 550-141-850/0699