Part number 550-141-850/0699

Installation • Start-Up • Parts • Maintenance

CHART 8 — Insufficient heat or no heat to system (POWER light on steady)

Electrical shock hazard — Wherever you see TURN OFF POWER, follow the instructions. Failure to follow instructions could result in severe personl injury, death or substantial property damage.

• Has it been at least 5 minutes since setting thermostat to

 

 

 

 

 

 

Is boiler System circulator operating?

 

call for heat? If not, wait 5 minutes. Is system heating?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

Yes

 

• Is thermostat set to call for heat? Remove thermostat

 

 

 

 

 

 

 

 

 

 

wires at boiler and check continuity across the two wires.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If circuit isn't closed, check external thermostat (zone

 

 

 

 

Remove CIRCULATORS harness plug from

 

 

valve, relay, etc.) wiring. Correct problems and retry.

 

 

 

 

 

CIRCULATORS plug receptacle (Figure 34, Item

 

 

• Reconnect external thermostat wiring at boiler.

 

 

 

 

 

 

 

4). Check with voltmeter across left-side 120 VAC

 

 

Is thermostat circuit closed (continuity across wires)?

 

 

 

 

 

N and 120 VAC H pins of receptacle.

 

 

 

 

 

 

 

 

Does voltmeter show 120 VAC across pins?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are all red lights off?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace control

 

Repair/replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Boiler is in standby.

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

module.

 

 

circulator. Retest.

 

 

 

 

 

 

 

 

 

• Set thermostat to call for heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Retest.

 

Repair/replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and recheck operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

wiring. Retest.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Verify Sequence of operation,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wait 30 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 22.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are all red lights off?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wait 5 minutes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is FLAME light on?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

Yes

 

Replace control module.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Retest.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• If you have sufficient heat — boiler should be in normal

 

• Check block switch on top of boiler with continuity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operating sequence. (See normal sequence of operation,

 

checker.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 22.)

 

 

 

 

 

 

 

 

 

 

 

 

Are block switch contacts closed?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If you have less than sufficient heat —

 

 

 

 

 

No

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

Is vent or combustion air piping free of blockage?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Wait for cast iron block to

 

 

• Check limit switch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

contacts with continuity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cool to room temperature.

 

 

 

 

 

Correct conditions and

 

 

 

 

 

 

 

 

 

checker.

 

 

 

 

 

 

 

Contact your Weil-McLain

 

 

Are block switch

 

 

 

 

 

 

 

 

 

 

recheck operation.

 

 

 

 

 

 

 

Are limit switch

 

 

 

 

 

 

sales representative.

 

 

 

 

 

 

 

 

 

 

See Figure 22 for

 

 

 

contacts closed?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

contacts closed?

 

 

 

 

 

normal sequence of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation.

 

 

 

 

 

 

 

 

 

No

 

 

 

Yes

 

 

 

 

Yes

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Wait for boiler water to cool to temperature 20 to 30 ˚F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

lower than temperature set on limit switch.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are limit switch contacts closed?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace block

 

 

Replace control

 

 

 

Replace limit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

 

Yes

 

switch. Retest.

 

 

module. Retest.

 

 

 

switch. Retest.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boiler water temperature exceeded setting on limit switch

 

• Excessive block temperature has been reduced to safe

operating level. Check for low water level or mineral

 

 

 

 

 

with thermostat calling for heat. Boiler is OK. (See normal

 

deposits in sections. Correct before proceeding.

 

 

 

 

 

 

 

sequence of operation, Figure 22.)

 

• Restart boiler and check normal sequence of operation.

 

 

 

 

Also check operation of setting on limit switch (should be

 

(See normal sequence of operation, Figure 22.)

 

 

 

 

 

 

 

above 140˚F.).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

81

Page 81
Image 81
Weil-McLain 550-141-850/0599, GOLD DV WATER BOILER manual Is thermostat circuit closed continuity across wires?