Weil-McLain GOLD DV WATER BOILER manual XIe Troubleshooting — control module, Control Module

Models: GOLD DV WATER BOILER 550-141-850/0599

1 96
Download 96 pages 38.64 Kb
Page 70
Image 70
XIe Troubleshooting — control module

GOLD GV Water boiler series 3 — manual

XIe Troubleshooting — control module

Control Module

Make sure ground wiring is installed per wiring diagram. Good grounding is extremely important for proper operation.

Solder or water splatter between plugs and circuit board can cause improper operation of control module. Place a shield over the boiler internal controls and components during installation. Failure to comply could result in severe personal injury, death or substantial property damage.

Control indicator lights — lockout modes

See Charts 1 through 8 in this section for detailed trouble- shooting procedures.

To reset control after a lockout, turn off power at the 120 VAC service switch or turn down all thermostats. Wait 45 seconds. Then restore power or call for heat.

After an over-temperature lockout (POWER and LIMIT lights flashing), the control will only reset after interruption of 120 VAC for 45 seconds. (And temperature at return water temperature sensor must be below 240 °F.)

POWER light flashing alone

Usually indicates reversed polarity of 120 VAC power wires.

POWER and TSTAT CIRC lights flashing

Usually indicates stray voltage on external thermostat circuit wires or return water temperature entering boiler sections has not reached 130 °F within 20 minutes.

POWER and LIMIT light flashing alternately

85063

Non-lockout light conditions
TSTAT CIRC light flashing alone

Usually indicates that limit circuit failed to cut off boiler at high temperaure — return water temperature sensor has sensed water over 235 °F.

POWER and PRES SWITCH lights flashing

Usually indicates pressure switch is closed when it should not be, or pressure switch failed to close within 5 minutes of blower starting.

POWER and FLAME lights flashing

Usually indicates control has had three unsuccessful ignition attempts or sensed flame when it shouldn’t be there.

Usually indicates return water temperature sensor detects water at boiler return pipe less than 40 °F. Both internal circulators will run continuously, even with no call for heat, until temperature rises.

LIMIT light flashing alone

Usually indicates an open or shorted return water temperature sensor.

Troubleshooting the GCM

See Figure 34 for location of harness plug receptacles and plugs on the control module.

70

Part number 550-141-850/0699

Page 70
Image 70
Weil-McLain GOLD DV WATER BOILER manual XIe Troubleshooting — control module, Control Module, Non-lockoutlight conditions