Small space — installation with less clearance than Figure 1 – BUT – no less than below; air openings for combustion/ventilation must be as shown below even for direct vent system.

Flooring and foundation

Flooring

The GV boiler is approved for installation on combustible flooring, but must never be installed on carpeting.

TOP VIEW

Access DOOR with fresh air

openings

Wall

4"

Front

 

 

 

 

 

min

 

 

 

 

 

Wall

10"

min

Boiler 1"

top min

1" min

Wall

Do not install boiler on carpeting even if foundation is used. Fire can result, causing severe personal injury, death or substantial property damage.

Foundation

Provide a solid brick or minimum 2-inch thick concrete foundation pad if any of the following is true:

• floor can become flooded.

the boiler mounting area is not level.

high profile condensate pump is used.

 

(Foundation thickness will depend on height

 

of condensate pump inlet.) Refer to separate

Area adjacent to access door must be accessible

and must allow for removal of the GV boiler for service.

No other appliance or air mover (exhaust fan, etc.) may be mounted in the same space.

Weil-McLain supplement for details.

The minimum foundation size is 16" wide by:

30¾" long for GV-3 or GV-4.

37¾" long for GV-5 or GV-6.

SIDE VIEW

6" max

6" max

Ceiling

 

 

 

Access door

 

1"

 

 

 

 

 

 

 

 

 

 

 

4"

 

Front

 

min

 

 

 

 

side

 

 

 

 

 

 

 

 

 

Boiler

 

 

 

 

 

min

Floor

85006b

1"

Wall

 

 

 

 

min

Residential garage installation

Precautions

Take the following special precautions when installing the boiler in a residential garage. If the boiler is located in

a residential garage, per ANSI Z223.1, paragraph 5.1.9:

(2)Fresh air openings —

Each with at least 1 sq. inch per 1,000 Btuh of boiler input

Mount the boiler a minimum of 18 inches above the floor of the garage to assure the burner and ignition devices will be no less than 18 inches above the floor.

Locate or protect the boiler so it cannot be damaged by a moving vehicle.