the following guidelines to change the termination for your system:

Refer to the circuit board diagram on the previous page for details.

If the Base has multiple strings of relays radiating from it, the Base would not be terminated but each Relay would.

If the Base is first in a string, (not in the middle or end of a string), set the 422 jumpers to Base w/RS-422 termination.

The last Relay in each string should have its jumpers set as a Relay w/RS-422 termination. Any Relay that is not the last relay in the string would not be terminated.

Relay Station failures are often cable-related. If a Terminal puts out a “Who Can Hear Me?” message and a Relay that is for some reason not connected to the Base Station (bad cable, cut cable, broken connectors) hears it, it answers with the message:

Relay n Cannot Be

Heard by the Base

Notify Supervisor

Press Any Key

At this point, it is up to the operator to notify someone that the Relay is not communicating with the Base and to check the cabling first. There

is no message sent to the host, so it is very important that the operator that receives this message notify someone immediately.

B-6