York R-410A manual YTG-G-0708, ZJ/ZR/ZF Unit Dimensions Rain Hood, Rear View, LH View, Detail “Y”

Models: R-410A

1 104
Download 104 pages 7.39 Kb
Page 101
Image 101
ZJ/ZR/ZF Unit Dimensions Rain Hood

251934-YTG-G-0708

ZJ/ZR/ZF Unit Dimensions Rain Hood

 

Power Exhaust

Economizer Motorized

 

Supply Air

Rain Hood

Damper Rain Hood

 

(on Return

(on Outdoor

 

Compartment

Economizer/Motorized Damper

Air Compartment)

Air Compartment)

 

 

 

and Power Exhaust Rain Hood

36-5/8”

Fixed

Outdoor Air

Intake Hood

(Located on

Return Air

1” Condensate

Compartment)

5”

16-1/8” Rear View

Drain (Must be

Trapped)

28-3/16” LH View 92”

 

Rear View

 

LH View

 

 

 

Detail “Y”

 

 

 

 

Unit with Rain Hoods

 

 

ZJ/ZR/ZF180-300 Unit Clearances

 

 

 

 

 

 

 

 

 

Direction

 

Distance (in.)

Direction

Distance (in.)

 

Top1

 

72 With 36 Maximum

 

 

 

 

Horizontal Overhang (For

Right

36

 

 

 

Condenser Air Discharge)

 

 

 

Front

 

36

Bottom2

0

 

Rear

 

24 (W/O Economizer)

Left

24 (W/O Economizer)

 

 

49 (W/Economizer)

36 (W/Economizer)3

 

 

 

 

1.Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.

2.Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.

3.If economizer is factory installed, the unassembled rain hood must be removed from its ride along position in front of the evaporator coil, or in the outdoor air compartment, prior to final installation.

Note: ELEC/ELEC Models: Units and ductwork are approved for zero clearance to combustible material when equipped with electric heaters.

GAS/ELEC Models: A 1" clearance must be provided between any combustible material and the supply air ductwork for a distance of 3 feet from the unit.

The products of combustion must not be allowed to accumulate within a confined space and recirculate. Locate unit so that the vent air outlet hood is at least:

Three (3) feet above any force air inlet located within 10 horizontal feet (excluding those integral to the unit).

Four (4) feet below, four horizontal feet from, or one foot above any door or gravity air inlet into the building.

Four (4) feet from electric and gas meters, regulators and relief equipment.