Page 65
Image 65
RPM Selection

251934-YTG-G-0708

RPM Selection

Size

Model

HP

Max

Motor

Blower

6 Turns

5 Turns

4 Turns

3 Turns

2 Turns

1 Turn

Fully

(Tons)

BHP

Sheave

Sheave

Open

Open

Open

Open

Open

Open

Closed

 

 

180

ZJ/ZF

5

5.75

1VP65

BK110

815

850

885

920

950

985

N/A

(15)

5

5.75

1VP65

BK090

1010

1055

1095

1135

1180

1220

N/A

 

210

ZJ/ZF

5

5.75

1VP60

BK110

730

765

800

835

870

905

N/A

(17.5)

7.5

8.63

1VP60

BK090

905

950

990

1035

1075

1120

N/A

 

240

ZJ/ZF

5

5.75

1VP60

BK110

730

765

800

835

870

905

N/A

(20)

7.5

8.63

1VP60

BK090

905

950

990

1035

1075

1120

N/A

 

300

 

7.5

8.63

1VP60

1B5V94

810

850

885

920

960

1000

N/A

ZJ/ZF

10

11.50

1VP75X

1B5V110

975

1005

1040

1070

1100

1135

1165

(25)

 

15

17.25

1VP75X

1B5V94

1140

1180

1215

1255

1290

1330

1365

 

 

180

ZR

5

5.75

1VP65

BK110

815

850

885

920

950

985

N/A

(15)

7.5

8.63

1VP65

BK090

1010

1055

1095

1135

1180

1220

N/A

 

240

ZR

7.5

8.63

1VP60

BK110

730

765

800

835

870

905

N/A

(20)

10

11.50

1VP60

BK090

905

950

990

1035

1075

1120

N/A

 

300

 

7.5

8.63

1VP60

1B5V94

810

850

885

920

960

1000

N/A

ZR

10

11.50

1VP75X

1B5V110

975

1005

1040

1070

1100

1135

1165

(25)

 

15

17.25

1VP75X

1B5V94

1140

1180

1215

1255

1290

1330

1365

 

 

Additional Static Resistance

Size

Model

CFM

Cooling Only1

Economizer2 3

 

Electric Heat kW2

 

(Tons)

18

36

54

72

 

 

 

 

180

ZJ

4500

0.10

0.10

0.10

0.10

0.20

0.20

ZR

6000

0.10

0.10

0.10

0.20

0.30

0.40

(15)

ZF

7500

0.10

0.10

0.10

0.30

0.40

0.60

 

 

 

6000

0.10

0.10

0.10

0.10

0.20

0.20

210 (17.5)

ZJ

7500

0.10

0.10

0.10

0.20

0.30

0.40

240 (20)

ZR

9000

0.15

0.15

0.10

0.30

0.40

0.60

300 (25)

ZF

10500

0.15

0.15

0.20

0.40

0.60

0.80

 

 

12000

0.20

0.20

0.30

0.50

0.70

0.90

1.Add these values to the available static resistance in the respective Blower Performance Tables.

2.Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.

3.The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.

Johnson Controls Unitary Products

65

Page 65