ZJ180 (15 Ton) (Continued)
Air on |
|
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
|
| |||||
Evaporator Coil | Total | Total |
| Sensible Capacity (MBh) |
| Total | Total |
| Sensible Capacity (MBh) |
| ||||||||
CFM |
| WB | Capacity1 | Input |
| Return Dry Bulb (°F) |
| Capacity1 | Input |
| Return Dry Bulb (°F) |
| ||||||
| (°F) | (MBh) | (kW)2 |
|
|
|
|
|
| (MBh) | (kW)2 |
|
|
|
|
|
| |
| 90 | 85 | 80 | 75 | 70 | 65 | 90 | 85 | 80 | 75 | 70 | 65 | ||||||
|
|
|
|
|
| 115°F |
|
|
|
|
|
|
| 125°F |
|
|
|
|
|
| 77 | 180.3 | 17.1 | 78.5 | 67.6 | 49.8 | - | - | - | 166.8 | 18.9 | 68.4 | 61.1 | 43.5 | - | - | - |
3750 |
| 72 | 167.2 | 16.9 | 111.3 | 93.5 | 75.7 | 57.9 | - | - | 154.4 | 18.7 | 105.1 | 87.6 | 70.0 | 52.4 | - | - |
| 67 | 154.0 | 16.8 | 144.1 | 119.5 | 101.7 | 83.9 | 66.1 | - | 141.9 | 18.6 | 141.9 | 114.0 | 96.5 | 78.9 | 61.3 | - | |
|
| |||||||||||||||||
|
| 62 | 143.0 | 16.6 | 143.0 | 143.0 | 124.7 | 106.9 | 89.1 | 71.3 | 131.7 | 18.4 | 131.7 | 131.7 | 120.0 | 100.6 | 83.0 | 65.5 |
|
| 77 | 186.6 | 17.0 | 95.7 | 75.3 | 54.8 | - | - | - | 172.7 | 18.8 | 89.1 | 68.5 | 48.1 | - | - | - |
|
| 72 | 173.0 | 16.8 | 124.3 | 103.8 | 83.4 | 62.9 | - | - | 159.8 | 18.6 | 118.0 | 97.7 | 77.3 | 57.0 | - | - |
4500 |
| 67 | 159.5 | 16.7 | 152.9 | 132.4 | 111.9 | 91.5 | 71.0 | - | 146.9 | 18.4 | 146.9 | 126.9 | 106.6 | 86.2 | 65.9 | - |
|
| 62 | 148.0 | 16.5 | 148.0 | 148.0 | 137.3 | 116.8 | 96.4 | 75.9 | 136.4 | 18.3 | 136.4 | 136.4 | 130.6 | 110.2 | 89.9 | 69.6 |
|
| 57 | 149.2 | 16.6 | 149.2 | 149.2 | 132.8 | 112.4 | 91.9 | 71.5 | 139.1 | 18.4 | 139.1 | 139.1 | 123.0 | 102.7 | 82.3 | 62.0 |
|
| 77 | 193.0 | 16.8 | 113.0 | 83.0 | 59.8 | - | - | - | 178.6 | 18.6 | 109.8 | 75.8 | 52.7 | - | - | - |
|
| 72 | 178.9 | 16.7 | 137.3 | 114.2 | 91.0 | 67.9 | - | - | 165.3 | 18.4 | 130.9 | 107.8 | 84.7 | 61.6 | - | - |
5250 |
| 67 | 164.9 | 16.5 | 161.6 | 145.3 | 122.2 | 99.1 | 76.0 | - | 152.0 | 18.3 | 152.0 | 139.8 | 116.7 | 93.6 | 70.5 | - |
|
| 62 | 153.1 | 16.4 | 153.1 | 153.1 | 149.9 | 126.8 | 103.7 | 80.5 | 141.1 | 18.1 | 141.1 | 141.1 | 141.1 | 119.9 | 96.8 | 73.7 |
|
| 57 | 154.2 | 16.5 | 154.2 | 154.2 | 145.0 | 121.9 | 98.8 | 75.6 | 143.8 | 18.2 | 143.8 | 143.8 | 134.7 | 111.6 | 88.5 | 65.4 |
|
| 77 | 199.3 | 16.7 | 130.3 | 90.7 | 64.9 | - | - | - | 184.5 | 18.5 | 130.5 | 83.2 | 57.3 | - | - | - |
|
| 72 | 184.8 | 16.6 | 150.3 | 124.5 | 98.7 | 72.9 | - | - | 170.8 | 18.3 | 143.7 | 117.9 | 92.0 | 66.2 | - | - |
6000 |
| 67 | 170.3 | 16.4 | 170.3 | 158.3 | 132.5 | 106.7 | 80.9 | - | 157.0 | 18.1 | 157.0 | 152.6 | 126.8 | 100.9 | 75.1 | - |
|
| 62 | 158.1 | 16.3 | 158.1 | 158.1 | 162.5 | 136.7 | 110.9 | 85.1 | 145.8 | 18.0 | 145.8 | 145.8 | 145.8 | 129.5 | 103.6 | 77.8 |
|
| 57 | 159.3 | 16.3 | 159.3 | 159.3 | 157.2 | 131.4 | 105.6 | 79.8 | 148.6 | 18.1 | 148.6 | 148.6 | 146.4 | 120.5 | 94.7 | 68.8 |
|
| 72 | 186.1 | 16.6 | 158.7 | 131.5 | 104.3 | 77.0 | - | - | 171.7 | 18.3 | 152.1 | 124.8 | 97.5 | 70.2 | - | - |
6600 |
| 67 | 171.5 | 16.4 | 171.5 | 165.5 | 140.0 | 112.7 | 85.5 | - | 157.9 | 18.1 | 157.9 | 157.9 | 134.2 | 106.9 | 79.7 | - |
| 62 | 159.2 | 16.3 | 159.2 | 159.2 | 161.4 | 134.2 | 106.9 | 79.7 | 146.6 | 18.0 | 146.6 | 146.6 | 146.6 | 124.1 | 96.8 | 69.5 | |
|
| |||||||||||||||||
|
| 57 | 160.4 | 16.4 | 160.4 | 160.4 | 159.4 | 132.1 | 104.9 | 77.7 | 149.4 | 18.1 | 149.4 | 149.4 | 148.3 | 121.1 | 93.8 | 66.5 |
|
| 72 | 187.3 | 16.6 | 167.1 | 138.5 | 109.8 | 81.2 | - | - | 172.7 | 18.3 | 160.4 | 131.6 | 102.9 | 74.2 | - | - |
7200 |
| 67 | 172.6 | 16.4 | 172.6 | 172.6 | 147.4 | 118.8 | 90.1 | - | 158.8 | 18.2 | 158.8 | 158.8 | 141.7 | 113.0 | 84.2 | - |
| 62 | 160.3 | 16.3 | 160.3 | 160.3 | 160.3 | 131.6 | 102.9 | 74.3 | 147.4 | 18.0 | 147.4 | 147.4 | 147.4 | 118.7 | 90.0 | 61.2 | |
|
| |||||||||||||||||
|
| 57 | 161.5 | 16.4 | 161.5 | 161.5 | 161.5 | 132.8 | 104.2 | 75.5 | 150.3 | 18.1 | 150.3 | 150.3 | 150.3 | 121.6 | 92.8 | 64.1 |
1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.