Electric Heat Minimum Supply Air

251934-YTG-G-0708

Electric Heat Minimum Supply Air

Size

 

 

 

 

 

Minimum Supply Air (CFM)

 

 

Voltage

 

Heater kW

 

(Tons)

 

 

 

 

 

 

 

18

36

54

72

 

 

 

 

 

180

208/230-3-60

 

4500

4500

5000

5000

460-3-60

 

 

4500

4500

5000

4500

(15)

 

 

600-3-60

 

 

4500

4500

4500

4500

 

 

 

210

208/230-3-60

 

6000

6000

6000

6000

460-3-60

 

 

6000

6000

6000

6000

(17.5)

 

 

600-3-60

 

 

6000

6000

6000

6000

 

 

 

240

208/230-3-60

 

6000

6000

6000

6000

460-3-60

 

 

6000

6000

6000

6000

(20)

 

 

600-3-60

 

 

6000

6000

6000

6000

 

 

 

300

208/230-3-60

 

7500

7500

7500

7500

460-3-60

 

 

7500

7500

7500

7500

(25)

 

 

600-3-60

 

 

7500

7500

7500

7500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For units with VFD and electric heat, the speed of the indoor blower motor continues to be controlled by duct static pressure via the VAV control board.

If there are VAV boxes present in the duct system, the boxes must be driven to the full-open position using a customer-supplied power source to assure adequate airflow across electric heating elements or gas heat exchanger tubes.

Indoor Blower Specifications

Size

Model

 

 

Motor

 

 

Motor Sheave

 

Blower Sheave

Belt

 

 

 

 

 

Datum Dia.

 

 

Datum Dia.

 

 

(Tons)

HP

RPM

Eff.

SF

Frame

Bore (in.)

Model

Bore (in.)

Model

 

 

 

 

 

 

 

(in.)

 

 

(in.)

 

 

 

 

180

ZJ/ZF

5

1725

0.89

1.15

184T

5.2 - 6.4

1 1/8

1VP65

10.4

 

1

BK110

BX85

(15)

5

1725

0.89

1.15

184T

5.2 - 6.4

1 1/8

1VP65

8.4

 

1

BK090

BX81

 

 

210

ZJ/ZF

5

1725

0.89

1.15

184T

4.2 - 5.5

1 1/8

1VP60

10.4

 

1 3/16

BK110

BX78

(17.5)

7.5

1725

0.91

1.15

213T

4.2 - 5.5

1 3/8

1VP60

8.4

 

1 3/16

BK090

BX75

 

 

240

ZJ/ZF

5

1725

0.89

1.15

184T

4.2 - 5.5

1 1/8

1VP60

10.4

 

1 3/16

BK110

BX78

(20)

7.5

1725

0.91

1.15

213T

4.2 - 5.5

1 3/8

1VP60

8.4

 

1 3/16

BK090

BX75

 

 

300

 

7.5

1725

0.91

1.15

213T

4.2 - 5.5

1 3/8

1VP60

9.5

 

1 7/16

1B5V94

BX78

ZJ/ZF

10

1725

0.89

1.15

215T

5.8 - 7.0

1 3/8

1VP75X

11.1

 

1 7/16

1B5V110

5VX840

(25)

 

 

15

1725

0.91

1.15

254T

6.2 - 7.4

1 5/8

1VP75X

9.5

 

1 7/16

1B5V94

5VX860

 

 

 

180

ZR

5

1725

0.89

1.15

184T

5.2 - 6.4

1 1/8

1VP65

10.4

 

1

BK110

BX85

(15)

7.5

1725

0.91

1.15

213T

5.2 - 6.4

1 3/8

1VP65

8.4

 

1

BK090

BX81

 

 

240

ZR

7.5

1725

0.91

1.15

213T

4.2 - 5.5

1 3/8

1VP60

10.4

 

1 3/16

BK110

BX78

(20)

10

1725

0.89

1.15

215T

4.2 - 5.5

1 3/8

1VP60

8.4

 

1 3/16

BK090

BX75

 

 

300

 

7.5

1725

0.91

1.15

213T

4.2 - 5.5

1 3/8

1VP60

9.5

 

1 7/16

1B5V94

BX78

ZR

10

1725

0.89

1.15

215T

5.8 - 7.0

1 3/8

1VP75X

11.1

 

1 7/16

1B5V110

5V840

(25)

 

 

15

1725

0.91

1.15

254T

6.2 - 7.4

1 5/8

1VP75X

9.5

 

1 7/16

1B5V94

5VX860

 

 

 

Power Exhaust Specifications

Voltage

 

Motor

 

 

Motor

 

CFM @

HP

RPM1

QTY

LRA

FLA

MCA

0.2 ESP

 

208/230-1-60

3/4

1075

1

7.7

5.0

6.25

5250

460-1-60

3/4

1075

1

4.1

2.2

2.75

5250

575-1-60

3/4

1050

1

2.84

1.5

1.875

5250

1. Motors are multi-tapped and factory wired for high speed.