THERMOSTAT
TERMINALS
CONTROL TERMINAL BLOCK
W1
W2
Y1
Y2
G
R
C
4
RC
1
2
5
W1
W2
Y1
G
OCC
P
P1
Y2
X
R
SD
C
Smoke
Detector
RJumper 3
SD
OCC
SD
24 VAC
6
X
TERMINALS ON
ALIMITED NUMBER OF
THERMOSTATS
1Second stage heating not required on single stage heating units.
2Second stage cooling not required on single stage cooling units.
3Jumper is required if there is no Smoke Detector circuit.
4Jumper is required for any combination of R, RC, or RH.
5OCC is an output from the thermostat to indicate the Occupied condition.
6X is an input to the thermostat to display Error Status conditions.
C
Class 2