York R-410A manual ZF180-300Physical Data Continued, ZJ/ZR/ZF180-300Unit Limitations

Models: R-410A

1 104
Download 104 pages 7.39 Kb
Page 20
Image 20
ZF180-300 Physical Data (Continued)

251934-YTG-G-0708

ZF180-300 Physical Data (Continued)

Component

 

 

 

 

 

 

Models

 

 

 

 

 

 

ZF180

ZF210

ZF240

 

 

ZF300

 

 

 

 

 

Nominal Tonnage

 

15

17.5

20

 

 

25

 

 

CONDENSER FAN DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity

 

2

 

2

2

 

 

2

 

 

Fan diameter (Inch)

 

24

 

24

30

 

 

30

 

 

Type

Prop

Prop

Prop

 

 

Prop

 

Drive type

Direct

Direct

Direct

 

 

Direct

 

No. speeds

 

1

 

1

1

 

 

1

 

 

Number of motors

 

2

 

2

2

 

 

2

 

 

Motor HP each

1.25

1.25

1.25

 

1.25

 

 

RPM

1140

1140

1140

 

1140

 

 

Nominal total CFM

5765

7000

7000

 

7000

 

 

BELT DRIVE EVAP FAN DATA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity

 

1

 

1

1

 

 

1

 

 

Fan Size (Inch)

15 X 15

18 X 15

18 X 15

 

 

18 X 15

 

Type

Centrifugal

Centrifugal

Centrifugal

 

Centrifugal

 

Motor Sheave

1VP65

 

1VP65

1VP60

 

1VP60

1VP60

 

1VP60

1VP60

 

1VP75X

 

1VP75X

Blower Sheave

BK110

 

BK090

BK110

 

BK090

BK110

 

BK090

1B5V94

 

1B5V110

 

1B5V94

Belt

BX85

 

BX81

BX78

 

BX75

BX78

 

BX75

BX78

 

5VX840

 

5VX860

Motor HP each

5

 

5

5

 

7.5

5

 

7.5

7.5

 

10

 

15

RPM

1725

 

1725

1725

 

1725

1725

 

1725

1725

 

1725

 

1725

Frame size

184T

 

184T

184T

 

213T

184T

 

213T

213T

 

215T

 

254T

FILTERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quantity - Size

 

-

4 - 16 x 25 x 2

4 - 16 x 25 x 2

4 - 16 x 25 x 2

5 - 18 x 24 x 2

4 - 16 x 20 x 2

4 - 16 x 20 x 2

4 - 16 x 20 x 2

 

ZJ/ZR/ZF180-300 Unit Limitations

Size

 

 

 

Unit Limitations

 

Unit Voltage

 

Applied Voltage

Outdoor DB Temp

(Tons)

 

 

Min

 

Max

Max (°F)

 

 

 

180

208/230-3-60

187

 

252

125

460-3-60

432

 

504

125

(15)

 

575-3-60

540

 

630

125

 

 

210

208/230-3-60

187

 

252

125

460-3-60

432

 

504

125

(17.5)

 

575-3-60

540

 

630

125

 

 

240

208/230-3-60

187

 

252

125

460-3-60

432

 

504

125

(20)

 

575-3-60

540

 

630

125

 

 

300

208/230-3-60

187

 

252

125

460-3-60

432

 

504

125

(25)

 

575-3-60

540

 

630

125

 

 

20

Johnson Controls Unitary Products

Page 20
Image 20
York R-410A manual ZF180-300Physical Data Continued, ZJ/ZR/ZF180-300Unit Limitations