savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity™
Simplicity™
Novar® BAS Control - The Novar®
Johnson Controls BAS Control - The Johnson Control
CPC BAS Control - The Computer Process Controls Model
Honeywell BAS Control - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.
Field Installed Accessories
YORK® offers several equipment accessories for field installation, for the ZJ/ZR/ZF Series.
•Single Input Electronic Enthalpy Economizers - Includes a
The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must be
•Motorized Outdoor Air Intake Damper - Includes a
The rain hood is painted to match the basic unit and must be field assembled before installing.
•Roof Curbs -
These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped
They're designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.
•High Altitude Natural Gas - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.
•Propane - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.
•High Altitude Propane - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.
•Side Duct Flanges -
•Barometric Relief Damper - This damper accessory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.
•High Static Drive - May include a belt, blower pulley, motor pulley or a motor change to enhance blower performance.
•Enthalpy Accessory Control Kit - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
•Burglar Bars - Mount in the supply and return openings to prevent entry into the duct work.
•Flue Exhaust Extension Kit - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.
•Wood Skid - Allows unit to be handled with 90" forks.
•CO2 Sensor - Senses CO2 levels and automatically overrides the economizer when levels rise above the present limits.
•Coil Guard - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
•Phase Monitors - Designed to prevent unit damage. The phase monitor will shut the unit down in an
Guide Specifications
General
Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility.
York's ZJ/ZR/ZF units are convertible single package units. All models have four independent refrigerant circuits for efficient part load operation and maximum comfort control. Although the units are primarily designed for curb mounting on a roof, they
8 | Johnson Controls Unitary Products |