York R-410A manual ZJ210 17.5 Ton Continued

Models: R-410A

1 104
Download 104 pages 7.39 Kb
Page 24
Image 24
ZJ210 (17.5 Ton) (Continued)

251934-YTG-G-0708

ZJ210 (17.5 Ton) (Continued)

Air on

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

Evaporator Coil

Total

Total

 

Sensible Capacity (MBh)

 

Total

Total

 

Sensible Capacity (MBh)

 

CFM

 

WB

Capacity1

Input

 

Return Dry Bulb (°F)

 

Capacity1

Input

 

Return Dry Bulb (°F)

 

 

(°F)

(MBh)

(kW)2

 

 

 

 

 

 

(MBh)

(kW)2

 

 

 

 

 

 

 

90

85

80

75

70

65

90

85

80

75

70

65

 

 

 

 

 

 

115°F

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

77

230.9

19.1

108.4

87.7

63.4

-

-

-

222.4

21.1

112.0

81.5

59.3

-

-

-

5500

 

72

207.5

19.0

146.2

121.9

97.6

73.3

-

-

197.6

20.9

142.4

117.7

93.1

68.4

-

-

 

67

184.1

18.9

184.1

156.1

131.8

107.5

83.2

-

172.9

20.8

172.9

151.5

126.8

102.1

77.4

-

 

 

 

 

62

181.9

18.8

181.9

181.9

154.2

129.9

105.6

81.3

173.3

20.8

173.3

173.3

144.2

119.6

94.9

70.2

 

 

77

232.5

19.1

124.7

92.9

67.0

-

-

-

222.3

21.1

128.9

88.9

62.6

-

-

-

 

 

72

209.0

19.0

155.1

129.1

103.1

77.1

-

-

197.5

21.0

150.8

124.5

98.2

72.0

-

-

6000

 

67

185.4

18.9

185.4

165.2

139.2

113.2

87.3

-

172.7

20.8

172.7

160.1

133.8

107.6

81.3

-

 

 

62

183.3

18.9

183.3

183.3

162.8

136.9

110.9

84.9

173.2

20.8

173.2

173.2

152.3

126.0

99.7

73.4

 

 

57

181.7

18.9

181.7

181.7

163.1

137.2

111.2

85.2

173.9

20.8

173.9

173.9

154.3

128.0

101.7

75.5

 

 

77

234.2

19.2

141.1

98.2

70.5

-

-

-

222.3

21.1

145.8

96.3

65.9

-

-

-

 

 

72

210.5

19.1

163.9

136.2

108.6

80.9

-

-

197.4

21.0

159.2

131.3

103.4

75.5

-

-

6500

 

67

186.7

18.9

186.7

174.3

146.6

119.0

91.3

-

172.6

20.9

172.6

168.8

140.9

113.0

85.1

-

 

 

62

184.6

18.9

184.6

184.6

171.5

143.8

116.2

88.5

173.1

20.9

173.1

173.1

160.3

132.4

104.5

76.6

 

 

57

183.0

18.9

183.0

183.0

171.8

144.1

116.5

88.8

173.8

20.9

173.8

173.8

162.4

134.5

106.7

78.8

 

 

77

235.9

19.2

157.4

103.4

74.1

-

-

-

222.2

21.2

162.7

103.7

69.2

-

-

-

 

 

72

212.0

19.1

172.7

143.4

114.0

84.7

-

-

197.4

21.0

167.6

138.1

108.6

79.1

-

-

7000

 

67

188.1

19.0

188.1

183.4

154.0

124.7

95.3

-

172.5

20.9

172.5

172.5

147.9

118.5

89.0

-

 

 

62

185.9

19.0

185.9

185.9

180.1

150.8

121.5

92.1

173.0

20.9

173.0

173.0

168.3

138.8

109.3

79.8

 

 

57

184.3

18.9

184.3

184.3

180.5

151.1

121.8

92.4

173.8

20.9

173.8

173.8

170.6

141.1

111.6

82.1

 

 

72

217.1

19.1

186.2

154.2

122.3

90.3

-

-

202.0

21.0

180.5

148.5

116.5

84.5

-

-

7875

 

67

192.6

19.0

192.6

190.3

165.2

133.2

101.2

-

176.6

20.9

176.6

176.6

158.7

126.7

94.6

-

 

62

190.4

18.9

190.4

190.4

187.5

155.6

123.6

91.7

177.1

20.9

177.1

177.1

174.8

142.8

110.7

78.7

 

 

 

 

57

188.8

18.9

188.8

188.8

186.9

154.9

123.0

91.0

177.9

20.9

177.9

177.9

176.3

144.3

112.3

80.2

 

 

72

222.3

19.1

199.7

165.1

130.5

96.0

-

-

206.7

21.0

193.5

158.9

124.4

89.8

-

-

8750

 

67

197.2

19.0

197.2

197.2

176.3

141.7

107.1

-

180.6

20.9

180.6

180.6

169.4

134.9

100.3

-

 

62

194.9

18.9

194.9

194.9

194.9

160.4

125.8

91.2

181.2

20.9

181.2

181.2

181.2

146.7

112.1

77.6

 

 

 

 

57

193.3

18.9

193.3

193.3

193.3

158.7

124.1

89.6

182.0

20.9

182.0

182.0

182.0

147.5

112.9

78.4

1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.