ZR180-300 Bottom Duct Application

251934-YTG-G-0708

ZR180-300 Bottom Duct Application

ZR180 (15 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

 

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

2.2

2.4

2.6

(CFM)

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

 

Standard 5

HP & Field Supplied Drive

 

 

Standard 5 HP & Drive

 

 

 

 

 

High Static 7.5 HP & Drive

 

 

 

4000

735

1.20

773

1.46

813

1.70

855

1.92

897

2.12

939

2.30

982

2.47

1023

2.63

1064

2.78

1103

2.93

1140

3.07

1175

3.22

4400

767

1.56

805

1.83

845

2.07

886

2.28

929

2.48

971

2.66

1013

2.83

1055

2.99

1096

3.14

1135

3.29

1172

3.44

1207

3.58

4800

802

1.98

840

2.24

880

2.48

921

2.70

963

2.89

1006

3.08

1048

3.25

1090

3.40

1131

3.56

1170

3.70

1207

3.85

1242

3.99

5200

839

2.44

877

2.70

917

2.94

959

3.16

1001

3.35

1043

3.54

1086

3.70

1127

3.86

1168

4.01

1207

4.16

1244

4.31

1279

4.45

5600

879

2.94

917

3.21

957

3.44

998

3.66

1041

3.86

1083

4.04

1125

4.21

1167

4.37

1208

4.52

1247

4.67

1284

4.81

1319

4.96

6000

921

3.49

959

3.76

999

4.00

1040

4.21

1082

4.41

1125

4.59

1167

4.76

1209

4.92

1250

5.07

1289

5.22

1326

5.36

1361

5.51

6400

965

4.09

1003

4.35

1043

4.59

1084

4.81

1126

5.01

1169

5.19

1211

5.36

1253

5.51

1294

5.67

1333

5.81

1370

5.96

1405

6.11

6800

1010

4.72

1049

4.99

1089

5.23

1130

5.44

1172

5.64

1215

5.82

1257

5.99

1299

6.15

1339

6.30

1379

6.45

1416

6.59

1450

6.74

7200

1058

5.40

1096

5.66

1136

5.90

1177

6.12

1220

6.32

1262

6.50

1304

6.67

1346

6.82

1387

6.98

1426

7.12

1463

7.27

1498

7.42

7600

1107

6.11

1145

6.37

1185

6.61

1226

6.83

1269

7.03

1311

7.21

1353

7.38

1395

7.54

1436

7.69

1475

7.84

1512

7.98

1547

8.13

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5 HP & Field Supplied Drive

 

 

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.898.

ZR240 (20 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

 

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

2.2

2.4

2.6

(CFM)

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

 

 

 

 

 

Standard 7.5

HP & Drive

 

 

 

 

 

 

 

 

High Static 10 HP & Drive

 

 

 

 

5200

727

1.51

763

1.95

799

2.36

835

2.75

870

3.10

904

3.42

938

3.70

970

3.93

1001

4.11

1031

4.24

1059

4.32

1085

4.33

5600

750

1.96

786

2.39

822

2.81

857

3.19

892

3.55

927

3.86

960

4.14

993

4.37

1024

4.56

1054

4.69

1082

4.76

1108

4.77

6000

774

2.45

810

2.88

846

3.30

882

3.68

917

4.04

951

4.35

985

4.63

1017

4.86

1048

5.05

1078

5.18

1106

5.25

1132

5.26

6400

800

2.98

836

3.42

872

3.83

908

4.22

943

4.57

977

4.89

1011

5.16

1043

5.40

1074

5.58

1104

5.71

1132

5.78

1158

5.79

6800

828

3.56

864

4.00

899

4.41

935

4.80

970

5.15

1004

5.47

1038

5.74

1070

5.98

1102

6.16

1131

6.29

1159

6.36

1185

6.37

7200

857

4.19

892

4.62

928

5.03

964

5.42

999

5.77

1033

6.09

1067

6.37

1099

6.60

1130

6.79

1160

6.92

1188

6.99

1214

7.00

7600

887

4.86

923

5.29

958

5.71

994

6.09

1029

6.44

1063

6.76

1097

7.04

1129

7.27

1160

7.46

1190

7.59

1218

7.66

1244

7.67

8000

918

5.57

954

6.01

990

6.42

1025

6.81

1060

7.16

1095

7.48

1128

7.75

1161

7.99

1192

8.17

1222

8.30

1249

8.37

1276

8.38

8400

951

6.33

987

6.77

1022

7.18

1058

7.56

1093

7.92

1127

8.23

1161

8.51

1193

8.74

1224

8.93

1254

9.06

1282

9.13

1308

9.14

8800

984

7.13

1020

7.57

1056

7.98

1092

8.36

1127

8.72

1161

9.04

1195

9.31

1227

9.55

1258

9.73

1288

9.86

1316

9.93

1342

9.94

9200

1019

7.97

1055

8.41

1091

8.82

1126

9.21

1162

9.56

1196

9.88

1229

10.15

1262

10.39

1293

10.57

1323

10.70

1351

10.77

1377

10.79

9600

1055

8.85

1091

9.29

1127

9.70

1162 10.09

1197

10.44

1232

10.76

1265

11.04

1298

11.27

1329

11.45

-

-

-

-

-

-

10000

1092

9.78

1128

10.21

1164

10.62

1199

11.01

1234

11.36

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

10 HP & Field Supplied Drive

 

 

 

 

 

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.838.