ZF240 (20 Ton) (Continued)
Air on |
|
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
|
| |||||
Evaporator Coil | Total | Total |
| Sensible Capacity (MBh) |
| Total | Total |
| Sensible Capacity (MBh) |
| ||||||||
CFM |
| WB | Capacity1 | Input |
| Return Dry Bulb (°F) |
| Capacity1 | Input |
| Return Dry Bulb (°F) |
| ||||||
| (°F) | (MBh) | (kW)2 |
|
|
|
|
|
| (MBh) | (kW)2 |
|
|
|
|
|
| |
| 90 | 85 | 80 | 75 | 70 | 65 | 90 | 85 | 80 | 75 | 70 | 65 | ||||||
|
|
|
|
|
| 115°F |
|
|
|
|
|
|
| 125°F |
|
|
|
|
|
| 77 | 259.6 | 28.3 | 108.9 | 88.3 | 67.7 | - | - | - | 239.1 | 30.7 | 99.0 | 81.5 | 61.1 | - | - | - |
5000 |
| 72 | 242.3 | 27.7 | 146.8 | 126.2 | 105.6 | 85.0 | - | - | 224.6 | 30.0 | 140.1 | 119.7 | 99.2 | 78.8 | - | - |
| 67 | 225.0 | 27.1 | 184.8 | 164.2 | 143.6 | 122.9 | 102.3 | - | 210.0 | 29.3 | 178.3 | 157.8 | 137.4 | 116.9 | 96.5 | - | |
|
| |||||||||||||||||
|
| 62 | 207.6 | 26.7 | 207.6 | 207.2 | 174.1 | 153.5 | 132.9 | 112.3 | 193.3 | 28.9 | 193.3 | 193.3 | 165.0 | 144.6 | 124.1 | 103.7 |
|
| 77 | 267.9 | 28.3 | 120.8 | 97.4 | 74.1 | - | - | - | 246.8 | 30.6 | 113.8 | 90.5 | 67.2 | - | - | - |
|
| 72 | 250.0 | 27.7 | 162.3 | 139.0 | 115.6 | 92.3 | - | - | 231.8 | 29.9 | 155.7 | 132.4 | 109.2 | 85.9 | - | - |
6000 |
| 67 | 232.2 | 27.1 | 203.9 | 180.5 | 157.2 | 133.8 | 110.5 | - | 216.8 | 29.2 | 197.6 | 174.4 | 151.1 | 127.8 | 104.6 | - |
|
| 62 | 214.3 | 26.6 | 214.3 | 214.0 | 190.6 | 167.3 | 143.9 | 120.6 | 199.5 | 28.8 | 199.5 | 199.5 | 181.6 | 158.3 | 135.0 | 111.7 |
|
| 57 | 215.4 | 26.7 | 215.4 | 215.1 | 191.8 | 168.4 | 145.1 | 121.7 | 203.0 | 29.0 | 203.0 | 202.7 | 179.0 | 155.7 | 132.4 | 109.1 |
|
| 77 | 276.2 | 28.2 | 132.7 | 106.6 | 80.5 | - | - | - | 254.5 | 30.5 | 128.5 | 99.4 | 73.4 | - | - | - |
|
| 72 | 257.8 | 27.6 | 177.9 | 151.8 | 125.7 | 99.6 | - | - | 239.0 | 29.8 | 171.3 | 145.2 | 119.1 | 93.0 | - | - |
7000 |
| 67 | 239.4 | 27.0 | 223.0 | 196.9 | 170.8 | 144.7 | 118.6 | - | 223.5 | 29.1 | 217.0 | 190.9 | 164.8 | 138.7 | 112.7 | - |
|
| 62 | 220.9 | 26.6 | 220.9 | 220.8 | 207.2 | 181.1 | 155.0 | 128.9 | 205.7 | 28.7 | 205.7 | 205.7 | 198.1 | 172.0 | 145.9 | 119.8 |
|
| 57 | 222.0 | 26.7 | 222.0 | 221.9 | 208.4 | 182.3 | 156.2 | 130.1 | 209.3 | 28.9 | 209.3 | 209.2 | 195.3 | 169.2 | 143.1 | 117.0 |
|
| 77 | 284.5 | 28.2 | 144.7 | 115.8 | 86.9 | - | - | - | 262.2 | 30.4 | 143.3 | 108.4 | 79.5 | - | - | - |
|
| 72 | 265.6 | 27.6 | 193.4 | 164.6 | 135.7 | 106.9 | - | - | 246.3 | 29.7 | 186.8 | 157.9 | 129.0 | 100.1 | - | - |
8000 |
| 67 | 246.6 | 27.0 | 242.2 | 213.3 | 184.5 | 155.6 | 126.8 | - | 230.3 | 29.1 | 230.3 | 207.4 | 178.5 | 149.7 | 120.8 | - |
|
| 62 | 227.6 | 26.5 | 227.6 | 227.6 | 223.7 | 194.9 | 166.0 | 137.2 | 212.0 | 28.6 | 212.0 | 212.0 | 212.0 | 185.7 | 156.8 | 127.9 |
|
| 57 | 228.7 | 26.6 | 228.7 | 228.7 | 225.1 | 196.2 | 167.4 | 138.5 | 215.7 | 28.8 | 215.7 | 215.7 | 211.6 | 182.7 | 153.8 | 124.9 |
|
| 72 | 264.8 | 27.7 | 204.0 | 172.5 | 141.1 | 109.6 | - | - | 244.6 | 29.8 | 195.9 | 164.7 | 133.5 | 102.2 | - | - |
9000 |
| 67 | 245.9 | 27.1 | 243.6 | 223.2 | 191.7 | 160.3 | 128.8 | - | 228.7 | 29.1 | 228.7 | 216.0 | 184.7 | 153.5 | 122.2 | - |
| 62 | 226.9 | 26.6 | 226.9 | 226.9 | 225.0 | 193.5 | 162.0 | 130.5 | 210.5 | 28.7 | 210.5 | 210.5 | 210.5 | 180.6 | 149.3 | 118.1 | |
|
| |||||||||||||||||
|
| 57 | 228.0 | 26.7 | 228.0 | 228.0 | 226.2 | 194.7 | 163.2 | 131.8 | 214.2 | 28.9 | 214.2 | 214.2 | 212.2 | 180.9 | 149.7 | 118.5 |
|
| 72 | 263.9 | 27.8 | 214.6 | 180.5 | 146.4 | 112.3 | - | - | 242.9 | 29.9 | 205.1 | 171.5 | 137.9 | 104.3 | - | - |
10000 |
| 67 | 245.1 | 27.2 | 245.1 | 233.1 | 199.0 | 164.9 | 130.8 | - | 227.2 | 29.2 | 227.2 | 224.5 | 190.9 | 157.3 | 123.7 | - |
| 62 | 226.2 | 26.7 | 226.2 | 226.2 | 226.2 | 192.1 | 158.0 | 123.9 | 209.1 | 28.8 | 209.1 | 209.1 | 209.1 | 175.5 | 141.9 | 108.3 | |
|
| |||||||||||||||||
|
| 57 | 227.3 | 26.8 | 227.3 | 227.3 | 227.3 | 193.2 | 159.1 | 125.0 | 212.8 | 29.0 | 212.8 | 212.8 | 212.8 | 179.2 | 145.6 | 112.0 |
1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
46 | Johnson Controls Unitary Products |