ZF180 (15 Ton) (Continued)
Air on |
|
|
|
|
|
| Temperature of Air on Condenser Coil |
|
|
|
|
|
| |||||
Evaporator Coil | Total | Total |
| Sensible Capacity (MBh) |
| Total | Total |
| Sensible Capacity (MBh) |
| ||||||||
CFM |
| WB | Capacity1 | Input |
| Return Dry Bulb (°F) |
| Capacity1 | Input |
| Return Dry Bulb (°F) |
| ||||||
| (°F) | (MBh) | (kW)2 |
|
|
|
|
|
| (MBh) | (kW)2 |
|
|
|
|
|
| |
| 90 | 85 | 80 | 75 | 70 | 65 | 90 | 85 | 80 | 75 | 70 | 65 | ||||||
|
|
|
|
|
| 115°F |
|
|
|
|
|
|
| 125°F |
|
|
|
|
|
| 77 | 182.9 | 17.2 | 76.5 | 65.8 | 49.1 | - | - | - | 168.9 | 19.0 | 74.3 | 63.9 | 47.1 | - | - | - |
3750 |
| 72 | 166.4 | 17.0 | 108.9 | 92.2 | 75.5 | 58.8 | - | - | 153.5 | 18.6 | 106.2 | 89.4 | 72.6 | 55.9 | - | - |
| 67 | 149.8 | 16.8 | 141.2 | 118.6 | 101.9 | 85.2 | 68.5 | - | 138.0 | 18.3 | 138.0 | 114.9 | 98.2 | 81.4 | 64.6 | - | |
|
| |||||||||||||||||
|
| 62 | 137.8 | 16.6 | 137.8 | 130.9 | 108.7 | 92.0 | 75.3 | 58.6 | 127.1 | 18.1 | 127.1 | 117.2 | 96.9 | 80.1 | 63.4 | 46.6 |
|
| 77 | 188.9 | 17.2 | 91.3 | 72.5 | 53.7 | - | - | - | 173.9 | 19.0 | 91.3 | 70.1 | 51.3 | - | - | - |
|
| 72 | 171.8 | 17.0 | 120.1 | 101.3 | 82.5 | 63.7 | - | - | 158.0 | 18.6 | 116.7 | 97.9 | 79.1 | 60.3 | - | - |
4500 |
| 67 | 154.7 | 16.8 | 149.0 | 130.2 | 111.4 | 92.6 | 73.8 | - | 142.1 | 18.3 | 142.1 | 125.7 | 106.9 | 88.1 | 69.3 | - |
|
| 62 | 142.3 | 16.6 | 142.3 | 137.7 | 118.9 | 100.1 | 81.3 | 62.5 | 130.8 | 18.1 | 130.8 | 124.3 | 105.5 | 86.7 | 67.8 | 49.0 |
|
| 57 | 148.1 | 16.7 | 148.1 | 148.1 | 131.4 | 112.6 | 93.8 | 75.0 | 138.6 | 18.2 | 138.6 | 138.6 | 123.3 | 104.5 | 85.7 | 66.9 |
|
| 77 | 194.9 | 17.3 | 106.1 | 79.2 | 58.3 | - | - | - | 178.9 | 19.0 | 108.3 | 76.3 | 55.5 | - | - | - |
|
| 72 | 177.3 | 17.1 | 131.4 | 110.5 | 89.6 | 68.7 | - | - | 162.6 | 18.6 | 127.3 | 106.4 | 85.6 | 64.8 | - | - |
5250 |
| 67 | 159.7 | 16.8 | 156.8 | 141.9 | 121.0 | 100.1 | 79.1 | - | 146.2 | 18.3 | 146.2 | 136.5 | 115.7 | 94.9 | 74.0 | - |
|
| 62 | 146.9 | 16.7 | 146.9 | 144.6 | 129.1 | 108.2 | 87.3 | 66.4 | 134.6 | 18.1 | 134.6 | 131.3 | 114.0 | 93.2 | 72.3 | 51.5 |
|
| 57 | 152.8 | 16.7 | 152.8 | 152.8 | 142.7 | 121.7 | 100.8 | 79.9 | 142.7 | 18.2 | 142.7 | 142.7 | 133.3 | 112.5 | 91.7 | 70.8 |
|
| 77 | 201.0 | 17.3 | 120.9 | 85.9 | 62.9 | - | - | - | 184.0 | 19.0 | 125.2 | 82.6 | 59.7 | - | - | - |
|
| 72 | 182.8 | 17.1 | 142.7 | 119.7 | 96.7 | 73.7 | - | - | 167.2 | 18.6 | 137.8 | 114.9 | 92.1 | 69.2 | - | - |
6000 |
| 67 | 164.6 | 16.9 | 164.6 | 153.5 | 130.5 | 107.5 | 84.5 | - | 150.4 | 18.3 | 150.4 | 147.3 | 124.4 | 101.6 | 78.7 | - |
|
| 62 | 151.4 | 16.7 | 151.4 | 151.4 | 139.3 | 116.3 | 93.2 | 70.2 | 138.4 | 18.1 | 138.4 | 138.4 | 122.5 | 99.7 | 76.8 | 53.9 |
|
| 57 | 157.5 | 16.8 | 157.5 | 157.5 | 153.9 | 130.9 | 107.9 | 84.9 | 146.7 | 18.2 | 146.7 | 146.7 | 143.4 | 120.5 | 97.7 | 74.8 |
|
| 72 | 184.3 | 17.1 | 153.1 | 128.5 | 104.0 | 79.5 | - | - | 168.5 | 18.7 | 147.1 | 122.8 | 98.6 | 74.3 | - | - |
6750 |
| 67 | 166.0 | 16.9 | 166.0 | 160.5 | 140.4 | 115.9 | 91.4 | - | 151.6 | 18.3 | 151.6 | 150.8 | 133.2 | 108.9 | 84.7 | - |
| 62 | 152.7 | 16.7 | 152.7 | 152.7 | 146.6 | 122.1 | 97.6 | 73.0 | 139.5 | 18.1 | 139.5 | 139.5 | 131.6 | 107.3 | 83.0 | 58.7 | |
|
| |||||||||||||||||
|
| 57 | 158.9 | 16.8 | 158.9 | 158.9 | 157.1 | 132.5 | 108.0 | 83.5 | 147.9 | 18.3 | 147.9 | 147.9 | 146.2 | 121.9 | 97.7 | 73.4 |
|
| 72 | 185.9 | 17.2 | 163.4 | 137.4 | 111.3 | 85.3 | - | - | 169.8 | 18.7 | 156.5 | 130.8 | 105.0 | 79.3 | - | - |
7500 |
| 67 | 167.4 | 17.0 | 167.4 | 167.4 | 150.3 | 124.3 | 98.2 | - | 152.8 | 18.4 | 152.8 | 152.8 | 142.0 | 116.3 | 90.6 | - |
| 62 | 154.0 | 16.8 | 154.0 | 154.0 | 154.0 | 127.9 | 101.9 | 75.9 | 140.6 | 18.2 | 140.6 | 140.6 | 140.6 | 114.9 | 89.2 | 63.5 | |
|
| |||||||||||||||||
|
| 57 | 160.2 | 16.9 | 160.2 | 160.2 | 160.2 | 134.2 | 108.1 | 82.1 | 149.0 | 18.3 | 149.0 | 149.0 | 149.0 | 123.3 | 97.6 | 71.9 |
1.These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance Table for the kW of the supply air blower motor.
2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
42 | Johnson Controls Unitary Products |