York R-410A manual ZF180-300Bottom Duct Application, ZF180 15 Ton Bottom Duct

Models: R-410A

1 104
Download 104 pages 7.39 Kb
Page 62
Image 62
ZF180-300 Bottom Duct Application

251934-YTG-G-0708

ZF180-300 Bottom Duct Application

ZF180 (15 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

 

 

 

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

 

 

2.0

2.2

2.4

2.6

(CFM)

 

 

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

 

Standard 5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HP & Field

 

Standard 5 HP & Drive

 

 

 

 

 

 

High Static 5 HP & Drive

 

 

 

 

 

 

 

 

Supplied

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4400

803

1.70

841

2.00

877

2.28

919

2.52

991

2.84

1055

3.13

1110

3.38

1155

3.59

 

 

1193

3.78

1221

3.93

1242

4.04

1253

4.12

4800

832

2.11

870

2.42

906

2.69

948

2.93

1020

3.25

1084

3.54

1139

3.79

1185

4.01

 

 

1222

4.19

1250

4.34

1271

4.45

1282

4.53

5200

863

2.55

900

2.86

936

3.14

979

3.38

1051

3.70

1115

3.99

1169

4.24

1215

4.46

 

 

1253

4.64

1281

4.79

1301

4.90

1313

4.98

5600

896

3.03

933

3.34

969

3.62

1011

3.86

1084

4.19

1147

4.47

1202

4.73

1248

4.94

 

1285

5.13

1314

5.27

1334

5.39

1345

5.47

6000

930

3.54

967

3.86

1003

4.13

1045

4.38

1118

4.70

1181

4.99

1236

5.24

1282

5.46

 

-

-

-

-

-

-

-

-

6400

965

4.09

1002

4.41

1038

4.68

1081

4.93

1153

5.25

1217

5.54

-

-

-

-

 

-

-

-

-

-

-

-

-

6800

1002

4.67

1039

4.99

1075

5.27

1117

5.51

-

-

-

-

-

-

-

-

 

-

-

-

-

-

-

-

-

7200

1040

5.28

1077

5.60

-

-

-

-

-

-

-

-

-

-

-

-

 

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5 HP & Field Supplied Drive

 

 

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.838.

ZF210 (17.5 Ton) Bottom Duct

Air Flow

 

 

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

 

 

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

 

2.2

2.4

2.6

(CFM)

 

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

 

Standard

5 HP &

 

 

 

 

Standard 5 HP & Drive

 

 

 

 

 

 

High Static 7.5 HP & Drive

 

 

 

Field Supplied Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4400

661

0.74

697

1.19

733

1.62

768

2.03

803

2.40

838

2.73

871

3.02

904

3.26

935

3.45

 

964

3.59

992

3.66

1018

3.67

4800

677

1.07

712

1.53

748

1.96

784

2.36

819

2.73

853

3.06

887

3.35

919

3.59

950

3.79

 

980

3.92

1008

4.00

1034

4.01

5200

694

1.43

730

1.89

766

2.32

801

2.72

836

3.09

871

3.42

904

3.71

937

3.95

968

4.14

 

997

4.28

1025

4.35

1051

4.37

5600

713

1.82

749

2.27

785

2.71

820

3.11

856

3.48

890

3.81

923

4.10

956

4.34

987

4.53

 

1017

4.67

1045

4.74

1071

4.75

6000

734

2.25

770

2.70

806

3.13

841

3.53

877

3.90

911

4.23

944

4.52

977

4.77

1008

4.96

 

1038

5.09

1066

5.17

1092

5.18

6400

757

2.71

793

3.17

829

3.60

864

4.00

899

4.37

934

4.70

967

4.99

1000

5.23

1031

5.42

 

1060

5.56

1088

5.64

1114

5.65

6800

781

3.22

817

3.68

853

4.11

888

4.51

923

4.88

958

5.21

991

5.50

1024

5.74

1055

5.94

 

1085

6.07

1112

6.15

1139

6.16

7200

807

3.78

843

4.23

878

4.66

914

5.07

949

5.44

983

5.77

1017

6.06

1049

6.30

1081

6.49

 

1110

6.63

1138

6.70

1164

6.71

7600

834

4.38

870

4.83

905

5.26

941

5.67

976

6.04

1010

6.37

1044

6.66

1076

6.90

1108

7.09

 

1137

7.23

1165

7.30

1191

7.31

8000

862

5.02

898

5.48

934

5.91

969

6.31

1004

6.68

1039

7.01

1072

7.30

1105

7.55

1136

7.74

 

1166

7.87

1194

7.95

1220

7.96

8400

892

5.71

928

6.17

963

6.60

999

7.00

1034

7.37

1069

7.70

1102

7.99

1134

8.24

1166

8.43

 

1195

8.56

-

-

-

-

8800

923

6.45

959

6.91

994

7.34

1030

7.74

1065

8.11

1099

8.44

-

-

-

-

-

-

 

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Static 7.5 HP & Field Supplied Drive

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.838.

62

Johnson Controls Unitary Products

Page 62
Image 62
York R-410A manual ZF180-300Bottom Duct Application, ZF180 15 Ton Bottom Duct, ZF210 17.5 Ton Bottom Duct