York R-410A manual Airflow Performance, ZJ180-300Side Duct Application

Models: R-410A

1 104
Download 104 pages 7.39 Kb
Page 49
Image 49
Airflow Performance

251934-YTG-G-0708

Airflow Performance

ZJ180-300 Side Duct Application

ZJ180 (15 Ton) Side Duct

Air Flow

 

 

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

 

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

2.2

2.4

2.6

(CFM)

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

 

Standard 5

HP & Field Supplied Drive

 

 

Standard 5 HP & Drive

 

 

 

 

 

High Static 5

HP & Drive

 

 

 

4000

727

1.14

765

1.47

806

1.77

848

2.04

891

2.29

934

2.52

977

2.73

1020

2.93

1061

3.12

1101

3.30

1138

3.48

1174

3.67

4400

753

1.51

792

1.84

832

2.14

874

2.41

917

2.66

960

2.88

1004

3.09

1046

3.29

1087

3.48

1127

3.67

1165

3.85

1200

4.03

4800

781

1.92

820

2.25

861

2.55

903

2.82

946

3.06

989

3.29

1032

3.50

1074

3.70

1116

3.89

1155

4.08

1193

4.26

1228

4.44

5200

812

2.37

850

2.70

891

3.00

933

3.27

976

3.52

1019

3.74

1062

3.95

1105

4.15

1146

4.34

1186

4.53

1223

4.71

1259

4.89

5600

844

2.86

882

3.19

923

3.49

965

3.76

1008

4.01

1051

4.23

1094

4.45

1137

4.64

1178

4.83

1218

5.02

1255

5.20

1291

5.39

6000

877

3.39

916

3.72

957

4.02

999

4.29

1042

4.54

1085

4.76

1128

4.98

1170

5.17

1212

5.36

1251

5.55

1289

5.73

-

-

6400

912

3.96

951

4.29

992

4.59

1034

4.86

1077

5.10

1120

5.33

1163

5.54

1205

5.74

-

-

-

-

-

-

-

-

6800

949

4.56

988

4.89

1028

5.19

1070

5.46

1113

5.71

-

-

-

-

-

-

-

-

-

-

-

-

-

-

7200

986

5.20

1025

5.53

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5 HP & Field Supplied Drive

 

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.898.

ZJ210 (17.5 Ton) Side Duct

Air Flow

 

 

 

 

 

 

 

 

Available External Static Pressure - IWG1

 

 

 

 

 

 

 

 

 

 

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

 

2.2

2.4

2.6

(CFM)

 

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

 

RPM BHP

RPM BHP

RPM BHP

 

 

 

Standard 5

HP & Field Supplied Drive

 

 

 

Standard 5 HP & Drive

 

 

 

 

 

High Static 7.5 HP & Drive

 

 

4400

636

0.65

672

1.14

709

1.60

745

2.03

780

2.43

815

2.78

849

3.09

882

3.35

914

3.55

 

944

3.70

973

3.78

999

3.79

4800

649

0.99

685

1.48

721

1.94

757

2.37

793

2.77

828

3.12

862

3.43

895

3.69

927

3.89

 

957

4.04

985

4.12

1012

4.13

5200

663

1.34

700

1.83

736

2.29

772

2.72

808

3.11

843

3.47

877

3.78

910

4.04

942

4.24

 

972

4.39

1000

4.47

1027

4.48

5600

680

1.71

717

2.20

753

2.66

789

3.09

825

3.48

860

3.84

894

4.15

927

4.41

959

4.61

 

989

4.76

1017

4.84

1044

4.85

6000

699

2.11

735

2.60

772

3.06

808

3.49

844

3.88

879

4.24

913

4.55

946

4.80

977

5.01

 

1007

5.15

1036

5.24

1062

5.25

6400

719

2.55

756

3.03

792

3.49

828

3.92

864

4.32

899

4.67

933

4.98

966

5.24

998

5.45

 

1028

5.59

1056

5.67

1083

5.68

6800

742

3.02

778

3.51

814

3.97

850

4.40

886

4.79

921

5.15

955

5.46

988

5.72

1020

5.92

 

1050

6.07

1078

6.15

1105

6.16

7200

765

3.54

802

4.03

838

4.49

874

4.92

910

5.32

945

5.67

979

5.98

1012

6.24

1044

6.44

 

1074

6.59

1102

6.67

1129

6.68

7600

790

4.11

827

4.60

863

5.06

899

5.49

935

5.88

970

6.24

1004

6.55

1037

6.81

1069

7.01

 

1099

7.16

1127

7.24

1154

7.25

8000

817

4.72

853

5.21

890

5.67

926

6.10

962

6.50

997

6.85

1031

7.16

1064

7.42

1095

7.62

 

1125

7.77

1154

7.85

1180

7.86

8400

845

5.38

881

5.87

918

6.33

954

6.76

990

7.16

1025

7.51

1059

7.82

1092

8.08

1123

8.28

 

1153

8.43

1182

8.51

1208

8.52

8800

874

6.09

911

6.58

947

7.04

983

7.47

1019

7.86

1054

8.22

1088

8.53

-

-

-

-

 

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7.5 HP & Field Supplied Drive

1.Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.

2.See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.

3.kW = BHP x 0.838.

Johnson Controls Unitary Products

49

Page 49
Image 49
York R-410A manual Airflow Performance, ZJ180-300Side Duct Application