York R-410A manual YTG-G-0708, Johnson Controls Unitary Products, Minimum Circuit Ampacity

Models: R-410A

1 104
Download 104 pages 7.39 Kb
Page 71
Image 71
1.Minimum Circuit Ampacity.

251934-YTG-G-0708

ZJ180-300 - Standard Drive Without Powered Convenience Outlet (Continued)

 

 

Compressors

OD Fan

Supply

Pwr

 

 

 

 

 

 

Max Fuse2/

Size

 

Motors

Blower

Conv

 

Electric Heat Option

 

MCA1

Breaker3

Volt

 

(each)

 

 

 

(Tons)

 

 

(each)

Motor

Outlet

 

 

 

 

 

(Amps)

Size

 

 

 

 

 

 

 

 

 

 

 

 

RLA

LRA

 

MCC

FLA

FLA

FLA

Model

kW

Stages

 

Amps

 

(Amps)

 

 

 

 

 

 

 

 

 

None

-

-

 

-

106.3

110

 

 

 

 

 

 

 

 

 

E18

13.5

1

 

37.5

106.3

110

 

208-3-60

17.9

120

 

28.0

3.7

15.4

0.0

E36

27.0

2

 

74.9

112.9

125

 

 

 

 

 

 

 

 

 

E54

40.6

2

 

112.7

160.1

175

 

 

 

 

 

 

 

 

 

E72

54.1

2

 

150.2

169.4

200

 

 

 

 

 

 

 

 

 

None

-

-

 

-

105.3

110

 

 

 

 

 

 

 

 

 

E18

18.0

1

 

43.3

105.3

110

 

230-3-60

17.9

120

 

28.0

3.7

14.4

0.0

E36

36.0

2

 

86.6

126.3

150

 

 

 

 

 

 

 

 

 

E54

54.0

2

 

129.9

147.9

175

240

 

 

 

 

 

 

 

 

E72

72.0

2

 

173.2

191.2

225

(20)

 

 

 

 

 

 

 

 

None

-

-

 

-

55.6

60

 

 

 

 

 

 

 

 

 

E18

18.0

1

 

21.7

55.6

60

 

460-3-60

9.6

70

 

15.0

1.9

7.2

0.0

E36

36.0

2

 

43.3

63.1

70

 

 

 

 

 

 

 

 

 

E54

54.0

2

 

65.0

74.0

90

 

 

 

 

 

 

 

 

 

E72

72.0

2

 

86.6

95.6

110

 

 

 

 

 

 

 

 

 

None

-

-

 

-

43.4

50

 

 

 

 

 

 

 

 

 

E18

18.0

1

 

17.3

43.4

50

 

575-3-60

7.4

53

 

11.5

1.5

5.9

0.0

E36

36.0

2

 

34.6

50.7

60

 

 

 

 

 

 

 

 

 

E54

54.0

2

 

52.0

59.3

70

 

 

 

 

 

 

 

 

 

E72

72.0

2

 

69.3

76.7

90

 

 

 

 

 

 

 

 

 

None

-

-

 

-

141.8

150

 

 

 

 

 

 

 

 

 

E18

13.5

1

 

37.5

141.8

150

 

208-3-60

23.0

160

 

31.5

3.7

28.0

0.0

E36

27.0

2

 

74.9

141.8

150

 

 

 

 

 

 

 

 

 

E54

40.6

2

 

112.7

175.9

200

 

 

 

 

 

 

 

 

 

E72

54.1

2

 

150.2

185.2

200

 

 

 

 

 

 

 

 

 

None

-

-

 

-

139.3

150

 

 

 

 

 

 

 

 

 

E18

18.0

1

 

43.3

139.3

150

 

230-3-60

23.0

160

 

31.5

3.7

26.0

0.0

E36

36.0

2

 

86.6

140.8

150

 

 

 

 

 

 

 

 

 

E54

54.0

2

 

129.9

162.4

175

300

 

 

 

 

 

 

 

 

E72

72.0

2

 

173.2

205.7

225

(25)

 

 

 

 

 

 

 

 

None

-

-

 

-

72.7

80

 

 

 

 

 

 

 

 

 

E18

18.0

1

 

21.7

72.7

80

 

460-3-60

12.2

87

 

17.1

1.9

13.0

0.0

E36

36.0

2

 

43.3

72.7

80

 

 

 

 

 

 

 

 

 

E54

54.0

2

 

65.0

81.2

90

 

 

 

 

 

 

 

 

 

E72

72.0

2

 

86.6

102.9

110

 

 

 

 

 

 

 

 

 

None

-

-

 

-

53.7

60

 

 

 

 

 

 

 

 

 

E18

18.0

1

 

17.3

53.7

60

 

575-3-60

8.7

62

 

13.5

1.5

10.3

0.0

E36

36.0

2

 

34.6

56.2

60

 

 

 

 

 

 

 

 

 

E54

54.0

2

 

52.0

64.8

70

 

 

 

 

 

 

 

 

 

E72

72.0

2

 

69.3

82.2

90

1.Minimum Circuit Ampacity.

2.Dual Element, Time Delay Type.

3.HACR type per NEC.

Johnson Controls Unitary Products

71

Page 71
Image 71