Electric Heat Multipliers

251934-YTG-G-0708

Electric Heat Multipliers

 

Voltage

kW Capacity Multipliers1

Nominal

 

Applied

 

 

240

 

208

0.75

 

230

0.92

 

 

480

 

460

0.92

600

 

575

0.92

1.Electric heaters are rated at nominal voltage. Use this table to determine the electric heat capacity for heaters applied at lower voltages.

Sound Performance

ZJ/ZR/ZF Indoor Sound Power Levels

Size

 

ESP

 

Blower

 

 

Sound Power, dB (10-12) Watts

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

Sound Rating1

 

 

Octave Band Centerline Frequency (Hz)

 

 

(Tons)

(IWG)

 

 

 

 

 

 

 

 

 

RPM

BHP

dB (A)

63

125

 

250

500

1000

2000

 

4000

8000

 

 

 

 

 

 

180

6000

1

 

1080

4.6

89

99

99

 

89

82

84

77

 

72

67

(15)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

210

8000

1

 

1129

6.65

92

102

102

 

92

85

87

80

 

75

70

(17.5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

240

8000

1

 

1129

6.65

92

102

102

 

92

85

87

80

 

75

70

(20)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

300

10000

1.3

 

1160

12.5

98

108

108

 

98

91

93

86

 

81

76

(25)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data in any other form than sound power level ratings.